E6581301

Minimum resistance of connectable braking resistors

The minimum allowable resistance values of the externally connectable braking resistors are listed in the table below.

Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance values.

(For 200kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.)

Inverter

200V Class

400V Class

 

 

Related output capacity

Resistance of

Minimum allowable

Resistance of

Minimum allowable

 

 

(kW)

standard option

resistance

standard option

resistance

 

 

 

 

 

 

 

 

 

0.4

200￿

50￿

 

 

 

 

 

 

 

 

 

0.75

200￿

50￿

200￿

60￿

 

 

 

 

 

 

 

 

 

1.5

75￿

35￿

200￿

60￿

 

 

 

 

 

 

 

 

 

2.2

75￿

20￿

200￿

60￿

 

 

 

 

 

 

 

 

 

3.7/4.0

40￿

16￿

160￿

40￿

 

 

 

 

 

 

 

 

 

5.5

20￿

10￿

80￿

30￿

 

 

 

 

 

 

 

 

 

7.5

15￿

8￿

60￿

20￿

 

 

 

 

 

 

 

 

 

11

10￿

5￿

40￿

20￿

 

 

 

 

 

 

 

 

 

15

7.5￿

5￿

30￿

13.3￿

 

 

 

 

 

 

 

 

 

18.5

7.5￿

3.3￿

30￿

13.3￿

 

 

22

3.3￿

3.3￿

15￿

13.3￿

 

5

 

 

 

 

 

 

30

3.3￿

2.5￿

13.3￿

10￿

 

 

 

 

 

 

 

 

 

 

37

2￿

1.7￿

8￿

6.7￿

 

 

 

 

 

 

 

 

 

45

2￿

1.7￿

8￿

5￿

 

 

 

 

 

 

 

 

 

55

2￿

1.7￿

8￿

5￿

 

 

 

 

 

 

 

 

 

75

1.7￿

1.3￿

8￿

3.3￿

 

 

 

 

 

 

 

 

 

90

3.7￿

2.5￿

 

 

 

 

 

 

 

 

 

110

3.7￿

1.9￿

 

 

 

 

 

 

 

 

 

132

3.7￿

1.9￿

 

 

 

 

 

 

 

 

 

160

3.7￿

1.9￿

 

 

 

 

 

 

 

 

 

200

1.9￿

1￿

 

 

 

 

 

 

 

 

 

220

1.9￿

1￿

 

 

 

 

 

 

 

 

 

280

1.4￿

1￿

 

 

 

 

 

 

 

 

 

355

0.95￿

0.7￿

 

 

 

 

 

 

 

 

 

400

0.95￿

0.7￿

 

 

 

 

 

 

 

 

 

500

0.7￿

0.7￿

 

 

 

 

 

 

 

 

 

E-41

Page 111
Image 111
Toshiba VF-AS1 instruction manual Minimum resistance of connectable braking resistors