6.3Terminal function selection

6.3.1Keeping an input terminal function always active (ON)!

￿￿￿￿ , ￿￿￿￿ , ￿￿￿￿￿: Always ON function selection 1~3

• Function

This parameter specifies an input terminal function that is always kept active (ON). (Only one function selectable)

[Parameter setting]

Title

Function

Adjustment range

Default setting

￿￿￿￿￿

Always ON function selection 1

￿~￿￿￿

Inverter with a model number ending with

-WN, HN: ￿ -WP: ￿

 

 

 

￿￿￿￿￿

Always ON function selection 2

￿~￿￿￿

￿

￿￿￿￿￿

Always ON function selection 3

￿~￿￿￿

￿

*The selected function is always kept active regardless of the type of logic (positive or negative) in the table of function settings in 7.2.1.

6.3.2Modifying input terminal functions!

 

 

￿￿￿￿

: Input terminal function selection 1 (F)

￿￿￿￿

: Input terminal function selection 7 (S3)

 

 

 

 

 

 

 

 

 

 

￿￿￿￿

: Input terminal function selection 2

(R)

￿￿￿￿

: Input terminal function selection 8 (RR/S4)

 

 

 

 

 

 

 

 

 

 

￿￿￿￿

: Input terminal function selection 3

(ST)

￿￿￿￿

~

￿￿￿￿

:

 

 

 

 

 

 

 

 

 

￿￿￿￿

: Input terminal function selection 4 (RES)

 

 

Input terminal function selection 9~16

6

 

 

 

 

 

 

 

 

￿￿￿￿

: Input terminal function selection 5

(S1)

￿￿￿￿

~

￿￿￿￿

:

 

 

 

 

 

 

 

 

 

 

￿￿￿￿

: Input terminal function selection 6

(S2)

 

 

Input terminal function selection 17~20

 

￿For details, refer to Section 7.2.1.

Function

Use the above parameters to send signals from an external programmable controller to various control input terminals to operate and/or set the inverter.

The desired contact input terminal functions can be selected from 120 types (￿-￿￿￿). This gives system design flexibility.

Using the SW3 switch, the function of the RR/S4 terminal can be selected between analog input and contact input. By default, the RR/S4 terminal is set as an analog input terminal (voltage input terminal). To use it as a contact input terminal, you need to move the SW3 switch to the S4 position.

Setting of contact input terminal function

Terminal

Title

Function

 

Adjustment range

Default

symbol

 

setting

 

 

 

 

￿￿￿￿ [Note 3], ￿￿￿￿, ￿￿￿￿￿

Always ON function selection 1~3

 

 

￿￿

F

￿￿￿￿￿

Input terminal function selection 1

(F)

 

￿ (F)

R

￿￿￿￿￿

Input terminal function selection 2

(R)

￿~￿￿￿

￿ (R)

ST

￿￿￿￿ [Note 4], ￿￿￿￿￿

Input terminal function selection 3

(ST)

￿ (ST)

(￿ Refer to

RES

￿￿￿￿￿

Input terminal function selection 4

(RES)

￿ (RES)

Section 11.)

S1

￿￿￿￿￿

Input terminal function selection 5

(S1)

￿￿ (S1)

 

S2

￿￿￿￿￿

Input terminal function selection 6

(S2)

 

￿￿ (S2)

S3

￿￿￿￿￿

Input terminal function selection 7

(S3)

 

￿￿ (S3)

The terminal below is operative only when SW3 is in the S4 position.

 

RR/S4

￿￿￿￿￿

Input terminal function selection 7 (S4)

￿~￿￿￿ [Note 2]

￿￿ (S4)

Note 1: The function that has been selected using ￿￿￿￿, ￿￿￿￿and ￿￿￿￿ (always ON function selection 1~3 parameter) are always activated.

Note 2: When using the RR/R4 terminal as a contact input terminal (sink logic), always move the SW3 slide switch to the S4 position.

Note 3: VFAS1-****-WN, HN

Note 4: VFAS1-****-WP

F-6

Page 122
Image 122
Toshiba VF-AS1 Terminal function selection, Modifying input terminal functions, Setting of contact input terminal function