E6581301

Caution

Prohibited

Do not attach devices with built-in capacitors (such as noise filters or surge absorber) to the output (motor side) terminal.

This could cause a fire.

Preventing radio noise

To prevent electrical interference such as radio noise, separately bundle wires to the main circuit's power terminals (R/L1, S/L2, T/L3) and wires to the motor terminals (U/T1, V/T2, W/T3).

Control and main power supply

The control power supply and the main circuit power supply for the VF-AS1 are the same. If a malfunction or trip causes the main circuit to be shut off, control power will also be shut off.

2 If you want to keep the control circuit alive when the main circuit shuts off due to trouble or tripping, you use an optional control power supply backup unit (CPS002Z).

Wiring

Because the space between the main circuit terminals is small use sleeved pressure terminals for the connections. (stripped wires may be connected directly for 200V/18.5kW to 200V/45kW models and 400V/22kW to 400V/75kW models). Connect the terminals so that adjacent terminals do not touch each other.

For ground terminal G/E use wires of the size that is equivalent to or larger than those given in table below and always ground the inverter.

Use as large and short a ground wire as possible and wire it as close as possible to the inverter.

Voltage class

Applicable Motor

Grounding wire size

Grounding wire size

(AWG) [Note]

(mm2) [Note]

 

0.4~2.2 kW

14

2.5

 

3.7, 4.0 kW

12

4

 

5.5 kW

10

6

 

7.5 kW

10

10

200V

11, 15 kW

10

16

18.5, 22 kW

8

16

 

 

30 kW

6

25

 

37, 45 kW

6

35

 

55 kW

2

70

 

75 kW

2

95

 

0.75~4.0 kW

14

2.5

 

5.5 kW

12

2.5

 

7.5 kW

12

4

 

11 kW

10

6

 

15~22 kW

10

10

 

30 kW

10

16

 

37, 45 kW

8

16

 

55 kW

6

25

 

75 kW

6

35

400V

90 kW

2

70

 

110 kW

2

95

 

132 kW

1/0

95

 

160 kW

1/0

120

 

200 kW

1/0

150

 

220 kW

2/0

150

 

280 kW

3/0

120×2

 

355 kW

4/0

120×2

 

400 kW

4/0

150×2

 

500 kW

250MCM

150×2

Note1: The recommended cable size is that of the cable (e.g. 600V class, HIV cable) with continuous maximum permissible temperature of 75°C. Ambient temperatur e is 40°C or less and the wiring distance is 30m or less.

B-2

Page 44
Image 44
Toshiba VF-AS1 instruction manual Preventing radio noise, Control and main power supply, Wiring