E6581301!

 

 

 

14.Inspection and maintenance

Warning

Mandatory

The equipment must be inspected every day.

If the equipment is not inspected and maintained, errors and malfunctions may not be discovered which could lead to accidents.

Before inspection, perform the following steps.

(1)Shut off all input power to the inverter.

(2)Wait at least 15 minutes and check to make sure that the charge lamp is no longer lit.

(3)Use a tester that can measure DC voltages (800V DC or more), and check that the voltage to the DC main circuits (between PA/+ and PC/-) does not exceed 45V.

Performing an inspection without carrying out these steps first could lead to electric shock.

Be sure to inspect the inverter regularly and periodically to prevent it from breaking down because of the environment

of use, such as temperature, humidity, dust and vibration, or deterioration of its components with aging.

14.1Regular inspection

Electronic parts are easily affected by heat. Install the Inverter in a cool, well-ventilated, dust-free area for achieving

the original performance for a prolonged amount of time in demonstrate its original performance for a long time.

The purpose of regular inspections is to maintain the correct environment of use and to find any sign of failure or

malfunction by comparing current operation data with past operation records.

Subject of

 

Inspection procedure

 

inspection

 

Inspection item

Inspection

Inspection method

Criteria for judgment

 

cycle

 

 

 

 

 

 

 

1)

Dust, temperature

Occasionally

1) Visual check,

1) Improve bad points.

 

 

and gas

 

check by means of

2) Check for any trace of water

1.Indoor

2)

Drooping of water

Occasionally

a thermometer,

condensation.

 

and other liquid

 

smell check

3) Max. temperature:60°C

environment

 

 

3)

Room temperature

 

2) Visual check

 

 

Occasionally

 

 

 

 

3) Check by means of

 

 

 

 

 

 

 

 

 

 

a thermometer

 

 

1)

Vibration and noise

Occasionally

Tactile check of the

Is something unusual is found,

2.Component

 

 

 

cabinet

open the door and check the

 

 

 

 

transformer, reactors,

parts and

 

 

 

 

 

 

 

 

contactors, relays, cooling fan,

units

 

 

 

 

 

 

 

 

etc., inside. If necessary, stop

 

 

 

 

 

 

 

 

 

 

the operation.

 

1)

Load current

Occasionally

Moving-iron type AC

To be within the rated current,

3.Operation

 

 

 

ammeter

voltage and temperature.

data

2)

Voltage (*)

Occasionally

Rectifier type AC

No significant difference from

(output side)

 

 

 

voltmeter

data collected in a normal

 

 

 

 

 

state.

*: The voltage measured may slightly vary from voltmeter to voltmeter. When measuring the voltage, always take readings from the same circuit tester or voltmeter.

Check points

1.Something unusual in the installation environment

2.Something unusual in the cooling system

3.Unusual vibration or noise

4.Overheating or discoloration

5.Unusual odor

6.Unusual motor vibration, noise or overheating

7.Adhesion or accumulation of foreign substances (conductive substances)

Cautions about cleaning

To clean the inverter, wipe dirt off only its surface with a soft cloth but do not try to remove dirt or stains from any

 

14

other part. If stubborn stains persist, remove them by wiping gently with a cloth dampened with neutral detergent or

ethanol.

 

 

 

 

Never use any of the chemicals in the table below; the use of any of them may damage or peel the coating away from

 

 

molded parts (such as plastic covers and units) of the inverter.

 

 

 

 

 

 

 

 

Acetone

Ethylene chloride

Tetrachloroethane

 

 

Benzen

Ethyl acetate

Trichloroethylene

 

 

Chloroform

Glycerin

Xylene

 

 

N-1

Page 321
Image 321
Toshiba VF-AS1 instruction manual Regular inspection, Check points