E6581301
F-13
6

6.7

Operation frequency
6.7.1 Start frequency/Stop frequency!
!!
!
H
HH
H : Start frequency setting!
!!
!
H
HH
H : Stop frequency setting
H
HH
H : Start frequency"
""
"Stop frequency operation selection
[Parameter setting]
Title Function Adjustment range Default setting
H Starting frequency setting ~ Hz 
H Stop frequency setting ~ Hz 
H
Start frequency/Stop f requency op eration sel ection
"Stop operating
"Continue operating 
Start frequency setting H
Stop frequency setting H
Output frequency [Hz]
!
Time [s]
0
Note: Set these parameters so that the start frequency H is higher than the stop frequency H .
If the H -set frequency is lo wer than the H -set frequency, the reference frequency must be
higher than the H-set frequency to start the motor.
If both H and H are set to  Hz, the motor will start even if the frequency set is 0 .0Hz.
6.7.2 Run/Stop control with frequency setting signals
H
HH
H : Operation start frequency
H
HH
H : Operation start frequency hysteresis
• Function
The Run/Stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title!Function!Adjustment range!Default setting
!
H!Operation starting frequency!~HJ!!
H!Operation starting frequency hysteresis!~ Hz!!
Function
The frequency set with the parameter H is put out as soon as operation i s started.
Use the H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the s tarting frequency to a value
from 0.5 to 2.0Hz (max. 5Hz) is recommended. The occurrence of an overcurrent can be suppressed
by setting this frequency below the rated slippage of the motor. If 0 speed torque i s needed (RV=,
), set H, H at 0.0Hz.
• At start up : frequency set with H is put out immediately.
• At stop : The output frequency drops to 0Hz immediately by the frequency set with
H.
Use the H parameter when changing operation of the range of H#output frequency#
H.
The operation of the range of H#output frequency#H is following.
H
=
0
"
ing
by the condition
H
#
output frequency