•Motor control CPU is defective.

•Contact your Toshiba distributor.

 

 

 

 

•The drive circuit board in the

 

 

 

 

￿￿￿￿￿

Internal circuit

inverter was damaged.

 

 

 

 

 

error

•Power device is defective.

 

 

 

 

 

 

•Using braking function in not

•If the braking function is used, operate a motor in

 

 

 

 

￿￿=￿,￿,￿,￿,￿ mode

￿￿=￿,￿,￿,￿,￿ mode

 

 

 

 

•The control voltage between +SU

•Check whether the voltage between +SU and CC

 

 

 

Control power

and CC terminals is too low.

terminals is DC20V or more.

 

 

￿￿￿￿￿

backup

•Control power is not supplied

•Set ￿￿￿￿ to 0 if a control power backup device

 

 

 

undervoltage

through +SU and CC terminals.

is not connected to +SU and CC terminals.

 

 

 

error

•The parameter ￿￿￿￿ is not set

To reset the inverter that has been tripped

 

 

 

 

correctly.

because of this error, turn it off and then back on.

 

 

 

Step-out (for

•The motor shaft is locked.

•Unlock the motor shaft.

 

 

￿￿￿￿￿

PM motors

•One output phase is open.

•Check the interconnect cables between the

 

 

 

only)

•An impact load is applied.

inverter and the motor.

 

Note: Please contact us if you find any trips other than the above.

[Alarm] The following are messages only. No trip is developed.

Error

Problem

Possible causes

Remedies

 

 

code

 

 

 

 

 

 

 

 

•ST terminal is in open-circuit.

•Check SW1 select

 

￿￿￿￿

ST signal OFF

 

•Close ST-CC circuit (Sink logic)

 

 

 

 

•Close ST-P24/PLC circuit (Source logic)

 

 

 

•The control voltage between +SU

•Check whether the voltage between +SU and CC

 

 

 

and CC terminals is too low.

terminals is DC20V or more.

 

 

 

•Control power is not supplied

•Set ￿￿￿￿ to ￿ if a control power backup device

 

 

Control power

through +SU and CC terminals.

is not connected to +SU and CC terminals.

 

￿￿￿￿￿

backup

•The parameter ￿￿￿￿ is not set

In the event of a ￿￿￿￿ error, the inverter will not

 

 

undervoltage

correctly.

be reset automatically even if the control voltage

 

 

 

 

between +SU and CC terminals returns to its

 

 

 

 

normal level. To reset the inverter, turn it off and

 

 

 

 

then back it on.

 

 

 

•The supply voltage between R, S

•Measure the main circuit supply voltage.

 

￿￿￿￿￿

Undervoltage in

and T is under voltage.

If the voltage is at a normal level, the inverter

 

 

main circuit

•Trouble of rush current restraint

requires repairing.

 

 

 

circuit or DC circuit fuse.

•Contact your Toshiba distributor.

 

 

 

•The inverter is in the process of

•The inverter is normal if it restarts after several

 

￿￿￿￿￿

Retry

retry.

tens of seconds. The inverter restarts

 

•A momentary stop occurred.

automatically. Be careful of the machine because

 

 

 

 

 

 

 

 

it may suddenly restart.

 

 

Point setting

•The frequency setting signals at

•Set the frequency setting signals at points 1 and 2

 

￿￿￿￿￿

points 1 and 2 are set too close to

apart from each other.

 

 

alarm

each other.

 

 

 

 

 

 

 

 

￿￿￿￿￿

Key failure

•The same key is input continuously

•Check the operation panel.

 

 

alarm

more than 20 seconds.

 

 

 

 

 

•This message is displayed when

•Press the STOP key again to clear the trip.

 

 

Clear enabling

pressing the STOP key while an

 

 

 

￿￿￿￿

error code is displayed.

 

 

 

 

indication

• Input terminal RES signal is ON

•Turn off the input terminal RES signal.

 

 

 

 

 

 

 

during trip display.

 

 

 

 

Emergency stop

•The operation panel is used to

•Press the STOP key for an emergency stop. To

 

￿￿￿￿￿

enabling

stop the operation in automatic

cancel the emergency stop, press any other key.

 

 

indication

control or remote control mode.

 

 

 

 

Setting error

•An error is found in a setting when

•Check whether the setting is made correctly.

 

 

alarm

data is reading or writing.

 

 

 

 

An error code

 

 

 

 

￿￿/￿￿

 

 

 

13

and data are

 

 

 

 

displayed

 

 

 

 

alternately twice

 

 

 

 

 

each.

 

 

 

 

￿￿￿

DC braking

•DC braking in process

•The message goes off in several tens of seconds

 

•Field forcing in process

if no problem occurs. [Note]

 

 

 

 

 

￿￿￿￿￿

Shaft fixing in

•Motor shaft fixing control is in

•If the message disappears by stop command

 

 

control

process.

(ST-CC open), it is normal.

 

 

 

•The digit number of the item

•For indication of frequency, set multiplying rate

 

￿￿￿

 

displayed, e.g., frequency, is in

(￿￿￿￿) lower. (Parameter setting that results in

 

Panel indication

excess of the specified digit

overflow is of course valid.)

 

 

￿￿￿

 

￿￿￿

overflow

number.

 

 

 

 

 

(Number of overflowing digits is

 

 

 

 

 

indicated.)

 

 

 