E6581301!

B-5

2
[Standard connection diagram - sink logic]
The figure below shows an example of typical wiring in the main circuit 200V 55, 75kW/400V 90-280kW inverter.
*1: Be sure to connect the DC reactor.
*2: To supply a DC power, connect the cables to the PA/+ and PC/- terminals.
*3: If you want to use a DC power sup ply to operate the inver ter, be sure to contact your Toshiba distr ibutor, because an
inrush current limiting circuit is req uired in such a case.
*4: The noise filter is built in for models all of 400V.
*5: For models 200V-75kW and 400V-110kW or larger, three-phase power input is necessary to drive the fan if you want to use
a DC power supply.
*6: Every 200V model of any capacity and every 400V model with a capaci ty of 160kW or less come with dynamic braking uni t
drive circuits (GTR7) built into them as standard equipment, so if your invert er is among these models, connect an external
braking resistor (optional) alone.
*7: If you are using a 400V/200kW model or larger, use a braking unit (option al) and an external braking resistor (optional ) in
combination.
*8: Refer to Section 2.3.2 for switch functions.
*9: The functions assigned to terminals OUT1, VI/II and RR/S4 can be swit ched by changing parameter settings.
For details refer to Section 2.3.2.
*10: To supply control power from an external power supply for backing up the control po wer supplied from the inverter, an
optional control power backup device (CPS002Z) is required. In such a case , the backup device is used at the same ti me
with the internal power supply of the inverter.
The optional control power backup unit can be used with both 200V and 400V models.
To back up control power, set the parameter H (Control power supply backup option failure monitorin g) properly.
For more information, refer to 6.33.24.
*11: When RES-CC is shorted and then opened, the inverter protective status is reset.
*12:Be sure to short across
NO-CC