Install the inverter in a well-ventilated indoor place and mount it on a flat metal plate in portrait orientation.

If you are installing more than one inverter, the separation between inverters should be at least 5cm, and they should be arranged in horizontal rows.

If the inverters are horizontally arranged with no space between them (side-by-side installation), remove of the protective cover on top of the inverter. (200V-55kW or $%&'(& and 400V-90kW or larger models dose not need to remove the protective cover)

 

 

 

Standard installation

Side-by-side installation

 

 

 

 

 

 

H1 cm or more

 

H3 cm or more

 

 

 

 

 

 

 

 

 

 

*1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*2

 

 

 

 

 

 

 

 

 

 

 

 

 

5cm or more

5cm or more

 

 

 

 

 

 

 

 

 

 

H2 cm or more

 

 

H3 cm or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1

200V 0.4kW~15kW, 400V 0.75kW~18.5kW

 

 

 

 

 

*2

200V 18.5kW~45kW, 400V 22kW~75kW

 

 

 

 

 

 

 

 

 

 

 

 

 

H1(cm)

 

H2(cm)

 

H3(cm)

 

 

200V

75kW or smaller

10

 

10

(Note1)

 

10

(Note1)

 

 

400V

110kW or smaller

 

 

 

 

 

 

 

 

 

 

 

 

 

400V

132, 160kW

15

 

15

(Note1)

 

25

(Note1)

 

 

400V

200~280kW

20

 

15

(Note1)

 

25

(Note1)

 

 

400V

355, 400kW

30

 

25

(Note1)

 

25

(Note1)

 

 

400V

500kW

40

 

25

(Note1)

 

25

(Note1)

The space shown in the diagram is the minimum allowable clearance. Make the space on top and bottom as large as possible to allow for air passage.

Note1: For models designed for 200V-75kW and 400V-110kW motors or larger, leave a space of 30cm or more above and below the inverter.

Note2: Do not install in any location where there is high humidity or high temperatures and where there are large amounts of dust and metallic fragments. If you are going to install the equipment in any area that presents a potential problem, please consult with your Toshiba distributor before doing so.

Current reduction curve

Depending on the way in which the inverter is installed, the ambient temperature and the carrier frequency setting, you may need to reduce the inverter’s continuous output current.

Reduction rates vary depending on the capacity of the inverter. The capacities shown in these diagrams are capacities with the highest reduction rates. Refer to section 12, you can find 100 % value of output current there. The VFAS1 has the function of adjusting the inverter’s overload resistance automatically according to the ambient temperature, as shown in the figure below. This function enhances the inverter’s overload resistance when the ambient temperature is low. To use this function, set the parameter ￿￿￿￿ to ￿.

If ￿￿￿￿ is set to ￿ (default setting), protection will be provided by reducing the output current (approximate linear reduction) in ￿￿￿￿￿￿￿ 12, “Specifications,” by adjusting the PWM carrier frequency or at the occurrence of the event shown in the diagram below, which occurs first.

200V! 0.4)1.5)7.5kW

400V! 0.75)1.5kW

!

2Standard installation

2Side-by-side installation (without top cover)

 

 

 

 

Ambient temperature

 

 

 

 

Ambient temperature

Continuous

1103

 

 

4001Without top cover

Continuous

1103

 

 

 

 

 

 

500 (F631=0)

803

 

 

 

 

 

 

 

 

 

 

 

 

 

4001F631=1

 

1003

 

 

 

F631=1

 

1003

 

 

 

 

903

 

 

4001With top cover(F631=0)

 

903

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output

 

 

 

or

 

output

803

 

 

 

703

 

 

5001Without top cover

703

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

603

 

 

 

(F631=0)

 

 

 

 

 

current

 

 

 

 

current

603

 

 

 

503

 

 

6001Without top cover

503

 

 

 

 

 

 

 

 

 

 

600 (F631=0)

 

403

 

 

 

 

 

 

 

 

 

 

(F631=0)

 

403

 

 

 

 

4kHz

8kHz

12kHz

16kHz

 

 

4kHz

8kHz

12kHz

16kHz

 

 

 

 

 

 

 

 

Carrier frequency (￿￿)

 

 

Carrier frequency (￿￿)

A-24

Page 37
Image 37
Toshiba VF-AS1 Standard installation Side-by-side installation, 4001Without top cover, 5001Without top cover