E6581301!

2.3.2 Control circuit terminal block

The control circuit terminal block is common to all equipment.

!!

2

ST-CC Shorting bar (VFAS1-****-WN, HN) !

￿How to set input terminal function, refer to section 7.

Terminal

Input/

 

Function (Sink logic)

Function (Source logic)

Electrical specifications

symbol

output

 

VFAS1-****- H1,HN,WN

VFAS1-****-WP

 

 

 

 

 

Shorting across F-CC causes forward

Shorting across F-P24/PLC causes

Voltage free contact

F

Input

 

rotation; open causes deceleration

forward rotation; open causes

input

 

 

 

stop. (Across ST-CC is short state.)

deceleration stop.

24Vdc-5mA or less

 

 

 

Shorting across R-CC causes reverse

Shorting across R-P24/PLC causes

Lan current signal.

R

Input

 

rotation; open causes deceleration

reverse rotation; open causes

 

Choose low current

 

 

 

stop. (Across ST-CC is short state.)

deceleration stop.

 

 

 

contacts to avoid

 

 

 

The motor is on standby if ST and CC

The motor is on standby if ST and

 

 

Multifunction

poor ￿￿￿￿￿￿￿￿￿￿￿

 

 

are connected. It coasts to a stop if this

P24/PLC are connected. It coasts to a

ST

Input

 

 

 

 

connection is broken. This terminal can

stop if this connection is broken. This

*Sink/source selectable

 

 

 

 

 

 

be used for interlocking.

terminal can be used for interlocking.

with SW1

 

 

 

Shorting and then opening RES-CC

Shorting and then opening RES-

Sink input

 

 

programmable

cancels the status held by an inverter

P24/PLC cancels the status held by an

ON:Less than DC10V

RES

Input

protective function. When the inverter

inverter protective function. When the

OFF:DC16V or more

 

is operating normally, shorting and

inverter is operating normally, shorting

Source input

 

 

 

 

 

 

then opening RES-CC produces no

and then opening RES-P24/PLC

ON:DC11V or more

 

 

 

effect.

produces no effect.

OFF:Less than DC5V

S1

Input

contact

Shorting across S1-CC causes preset

Shorting across S1-P24/PLC causes

Note:

speed operation.

preset speed operation.

external power supply

 

 

 

Even when an

 

 

 

 

 

 

 

input

 

 

 

S2

Input

Shorting across S2-CC causes preset

Shorting across S2-P24/PLC causes

is used (in sink logic

speed operation.

preset speed operation.

mode, i.e., when

 

 

 

 

 

 

 

SINK (PLC) is

 

 

 

Shorting across S3-CC causes preset

Shorting across S3-P24/PLC causes

selected), connect the

S3

Input

 

reference

 

speed operation.

preset speed operation.

 

 

 

potential-side (0V

 

 

 

 

 

 

 

 

SW3: When SW3 is in the S4 position,

SW3: When SW3 is in the S4 position,

side) cable from the

RR/S4

Input

 

S4 and CC are shorted and preset

S4 and P24/PLC are shorted and preset

power supply to the

 

 

 

speed operation is selected.

speed operation is selected.

CC terminal.

SW1=SINK (INT): Sink logic!(When

!!!! the! internal! ! 24V power supply is used)!

 

If SW1 is set to 1

P24/PLC

 

SW1

 

SINK

SOURCE

 

P24

 

2.2kΩ

2.2kΩ

 

CC

 

SW1=SINK (PLC): Sink logic!(When an external 24V power supply is used)!

 

If SW1 is set to 2

P24/PLC

 

SW1

 

SINK

SOURCE

 

P24

 

2.2kΩ

2.2kΩ

 

CC

 

SW1=SOURCE (INT/PLC):! Source logic!(When the internal 24V power supply or an external 24V power

supply is used)!

If SW1 is set to 3

2.2kΩ

2.2kΩ

 

 

P24

SINK

SOURCE

SW1

 

P24/PLC

 

CC

 

B-11

Page 53
Image 53
Toshiba VF-AS1 instruction manual Res, RR/S4