E6581301

 

(Continued)

 

 

 

 

 

 

 

Requirements

Conducted noise

Conducted noise

 

 

Inverter type

PWM carrier

Length of motor

IEC61800-3 category C2

IEC61800-3 category C1

 

 

frequency￿￿￿￿

connecting cable

(EN55011 classA Group1)

(EN55011 classB Group1)

 

 

 

 

 

 

(kHz)

(m)

Applicable filters

Applicable filters

 

 

 

2~4

100

EMF3-4090F

EMF3-4090F

 

 

VFAS1-4220PL

300

EMF3-4090F

-

 

 

 

 

 

4.1~12

100

EMF3-4090F

EMF3-4090F

 

 

 

 

 

 

200

EMF3-4090F

-

 

 

 

 

 

 

 

2~2.5

100

EMF3-4092G

EMF3-4092G

 

 

VFAS1-4300PL

300

EMF3-4092G

-

 

 

 

 

 

VFAS1-4370PL

2.6~12

100

EMF3-4092G

EMF3-4092G

 

 

 

200

EMF3-4092G

-

 

 

 

 

 

 

 

2~2.5

100

EMF3-4180H

EMF3-4180H

 

 

VFAS1-4450PL~

300

EMF3-4180H

-

 

 

 

 

 

VFAS1-4750PL

2.6~12

100

EMF3-4180H

EMF3-4180H

 

 

 

200

EMF3-4180H

-

 

 

 

 

 

 

VFAS1-4900PC~

2.5

100

EMF3-4300I

-

 

 

VFAS1-4132KPC

 

 

 

 

 

 

 

 

VFAS1-4160KPC~

2.5

100

EMF3-4600J

-

 

 

VFAS1-4280KPC

 

 

 

 

 

 

 

 

VFAS1-4355KPC~

2.5

100

EMF3-4600J × 2

-

 

 

VFAS1-4500KPC

 

 

 

 

 

 

 

(2)Use shielded cables for the power and control cables, including filter input cables and inverter output cables. Route the cables and wires so as to minimize their lengths. Keep a distance between the power cable and the control cable and between the input and output wires of the power cable. Do not route them in parallel or bind them together, instead cross at right angle.

(3)Install the filter and the inverter in an enclosed steel cabinet, it is more effective in limiting the radiation. Earth the cabinet body securely with the thickest and shortest possible electric wire installed away from the power cables.

(4)Route the EMC filter input and output wires apart from each other.

(5)To limit the radiation noise from cables, earth each shielded cable to the EMC plate. It is effective to earth shielded cables in the vicinity of the inverter and filter (within a radius of 10cm from each of them). Inserting a ferrite core in a shielded cable is even more effective in limiting the radiation noise.

(6) To further limit the radiation noise, insert a zero-phase reactor in the inverter output line and insert ferrite cores in

9

the earth cables of the EMC plate and cabinet.

 

I-5

Page 236
Image 236
Toshiba VF-AS1 instruction manual VFAS1-4160KPC~ 100 EMF3-4600J, VFAS1-4355KPC~ 100 EMF3-4600J ×