Calorific values of the inverter and the required ventilation

The energy loss when the inverter converts power from AC to DC and then back to AC is about 5%. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the interior of the cabinet must be ventilated and cooled.

The amount of forced air-cooling ventilation required and the necessary heat exchange surface area when operating in a sealed cabinet according to motor capacity are as follows.

 

 

 

 

 

Part of inside

Amount of forced

Heat exchange surface

 

 

Voltage

Applicable Motor

Calorific values

calorific values

air cooling ventilation

area required for sealed

 

 

class

(kW)

(W)

(W)

required

storage cabinet

1

 

 

 

 

(note3)

(m3/min)

(m2)

 

 

0.4

50

25

0.29

1.0

 

 

 

0.75

70

28

0.40

1.4

 

 

 

1.5

113

32

0.65

2.3

 

 

 

2.2

135

39

0.78

2.7

 

 

 

3.7/4.0

191

40

1.1

3.8

 

 

 

5.5

307

60

1.8

6.2

 

 

 

7.5

408

72

2.4

8.2

 

 

200V

11

593

83

3.4

11.9

 

 

15

692

91

4.0

13.9

 

 

 

 

 

 

18.5

800

120

4.6

16.0

 

 

 

22

865

124

5.0

17.3

 

 

 

30

1140

152

6.6

22.8

 

 

 

37

1340

167

7.7

26.8

 

 

 

45

1570

185

9.0

31.4

 

 

 

55

1720

154

9.9

34.4

 

 

 

75

2210

154

12.7

44.2

 

 

 

0.75

57

28

0.33

1.2

 

 

 

1.5

82

30

0.47

1.7

 

 

 

2.2

112

33

0.64

2.3

 

 

 

3.7/4.0

136

41

0.78

2.8

 

 

 

5.5

262

58

1.5

5.3

 

 

 

7.5

328

66

1.9

6.6

 

 

 

11

448

77

2.6

9.0

 

 

 

15

577

104

3.3

11.6

 

 

 

18.5

682

106

3.9

13.7

 

 

 

22

720

111

4.2

14.4

 

 

 

30

980

134

5.6

19.6

 

 

 

37

1180

138

6.8

23.6

 

 

400V

45

1360

165

7.8

27.2

 

 

 

55

1560

179

9.0

31.2

 

 

 

75

2330

226

13.4

46.6

 

 

 

90

2410

237

13.8

48.2

 

 

 

110

2730

261

15.6

54.6

 

 

 

132

3200

296

18.3

64.0

 

 

 

160

3820

350

21.9

76.4

 

 

 

200

4930

493

28.2

98.6

 

 

 

220

5405

586

30.9

108.1

 

 

 

280

6830

658

39.1

136.6

 

 

 

355

7960

-

45.5

159.2

 

 

 

400

9300

-

53.2

186.0

 

 

 

500

11400

-

65.2

228.0

Note1: The heat loss for the optional external devices (input reactor, DC reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table. With the exception of inverters ￿￿￿￿￿￿￿￿￿￿ for motors with capacities of 355kW and more, in which case the calorific value of the DC reactor is included.

Note2: Each calorific value in the table refers to the quantity of heat that an inverter produces when it is operated continuously at the factory default ￿￿ (carrier frequency) under a load factor of 100%.

Note3: This value is power dissipated inside the enclosure ￿￿￿￿ using heatsink ￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿option.