E6581301

F-82

6
1) 2-wire RS485
The 2-wire RS485 device on the operation panel and the 4-wire RS485 device on the control circuit terminal
block are intended for data communications between inverters. To use an optional part for the RS48 5 device, it
should be connected to the communication connector (RJ45) on the operation panel. Through the 2-wire RS485
device!and a USB device (optional), the inverter can be linked to a co mputer.
!Here are the parts optionally available for the 2-wire RS485 device.
Optional USB-to-Serial conversion unit (Model: USB001Z)
Inverter-to-RS485/USB device interconnect cable (Model: CAB0011 (1m), CAB0013 (3m), CAB0015 (5m))
RS485/USB device-to-computer interconnect cable. Use a commercially available USB1.1 or 2.0 cable. (Type:
A-B, Cablelength: 0.25~1.5m)
Optional LED Remote Keypad (Model: RKP002Z)
Communication cable (Model:CAB0011 (1m), CAB0013 (3m), CAB0015 (5m))
Optional LCD Remote Keypad (Model: RKP004Z)
LCD special cable (Model:CAB0071 (1m), CAB0073 (3m), CAB0075 (5m), CAB00 710 (10m))
Note: Do not connect the cable (CAB0011, 0013 or 0015) from the communication device t o the optional LCD
Remote Keypad. Or the inverter or the optinol LCD Remote Keypad could be dama ged.
Setting for issuing run/stop commands from an external control device
Title Function Adjustment range Default setting Example of setting
EOQF Command mode selection ~
(Terminal input enabled)
(2-wire RS485)
Note: When parameter H (setting for communications between inverters) is used, the setting EOQF=
cannot be used for slave inverters.
Setting for issuing speed commands from an external control device
Title Function Adjustment range Default setting Example of setting
HOQF Frequency setting mode
selection 1 ~
(RR/S4 input)
(2-wire RS485)
Communication parameters (2-wire RS485)
These parameters allow you to change the communication speed, parity check set ting, inverter number,
communication error trip timer setting, etc. from the operation panel or an e xternal control device.
Title Function Adjustment range
Default setting
H
Communication speed (2
-
wire RS485)
:9600
bps,
:19200
bp
:38400
bps

H
Parity
(2-wire RS485)
:Non parity
,
:Even parity
:Odd parity 
H
Inverter number (common)
~
 
H
Communications time
-
out time
(common to 2-wire RS485 and 4-wire
RS485)
:OFF
~ sec. 
H
Communications time-out action *
(common to 2-wire RS485 and 4-wire
RS485)
Setting
2
-
wire
RS485
4
-
wire
RS485


No action
No action

Alarm
No action

Trip
No action

No action
Alarm

Alarm
Alarm

Trip
Alarm

No action
Trip

Alarm
Trip
Tri
p
Trip
H
Send waiting time
(2-wire RS485)

:Normal communications
~ sec. 
H
Master/slave setting for Inverter-to-inverter
communications
(2-wire RS485)
:Slave (issues a 0Hz command if
something goes wrong with the
master)
:Slave (continues operation if
something goes wrong with the
master)
:Slave (trips for emergency stop if
something goes wrong with the
master)
:Master (sends a frequency
command)
:Master (sends an output frequency)
:Master (sends a torque command)
:Master (sends an output torque
command)

H
P
rotocol selection (2
-
wire RS485)
:T
OSHIBA,
:MODBUS
 