E6581301
F-45
6
6.25 Torque limit
6.25.1 Torque limit switching
H
HH
H :
Power running torque limit 1
selection
H
HH
H :
Power running torque limit 1
level
H
HH
H :
Regenerative braking torque
limit 1 selection
H
HH
H :
Regenerative braking torque
limit 1 level
H
HH
H : P
ower running torque limit 2
level
H
HH
H :
Regenerative braking torque
limit 2 level
H
HH
H :
Power running torque limit 3
level
H
HH
H : Regenerative braking torque
limit 3 level
H
HH
H :
Power running torque limit 4
level
H
HH
H : Regenerative braking torque
limit 4 level
H
HH
H :
Constant output zone torque
limit selection
Function
This function is to decrease or increase the output frequency according to the loading condition when the
motor torque reaches the limit level. Setting a torque limit parameter at 250% means “Invalid.”
With this function, you can also select from between limiting the constant output or limiting the constant
torque in the constant output zone.
This function is not operate when the parameter RV=,, setting.
Setting methods
(1) When setting limits to torque, use internal parameters (Torque limits can also be set with an e xternal control
device.)
+250% torque
-250% torque

Power

running

Regenerative Forward run
H
H 

Regenerative

Power

running

H
H
Positive torque
Negative torque
Reverse run
: H=
: H=
With the parameter H, you can select the item that is limited in the cons tant output zone (somewhat weak
magnetic field) from between constant output (H=: default setting) and c onstant torque (H=).
When you select the constant torque limit option, you should preferably sel ect the output voltage limit option
(H=) with the parameter H (base frequency voltage selection).
Torque limits can be set with the parameters H and H.
[Setting of power running torque]
H (Power running torque limit 1 selection) : Set at (H)
H (Power running torque limit 1) : Set a desirable torque limit level.
[Setting of regenerative torque]
H (Regenerative braking torque limit 1 selection) : Set at (H )
H (Regenerative braking torque limit 1) : Set a desirable torque limit level.