K-45

!

[Output terminal function setting (1/3)]

 

Sensorless vector/vector with sensor (￿: valid, -: invalid)

Positive

Negative

Function

Speed control

Torque control

PM control

V/f

Reference

logic

logic

 

 

 

 

 

 

0

1

LL

￿/￿

￿/￿

￿

￿

 

2

3

UL

￿/￿

￿/￿

￿

￿

 

4

5

LOW

￿/￿

￿/￿

￿

￿

 

6

7

Acceleration/deceleration completion

￿/￿

-

￿

￿

 

8

9

Specified speed arrival

￿/￿

￿/￿

￿

￿

 

10

11

Failure FL (all trip)

￿/￿

￿/￿

￿

￿

 

12

13

Failure FL (except for EF, OCL, EPHO and OL2)

￿/￿

￿/￿

￿

￿

 

14

15

Overcurrent pre-alarm

￿/￿

￿/￿

￿

￿

 

16

17

Inverter overload pre-alarm

￿/￿

￿/￿

￿

￿

 

18

19

Motor overload pre-alarm

￿/￿

￿/￿

￿

￿

 

20

21

Overheat pre-alarm

￿/￿

￿/￿

￿

￿

 

22

23

Overvoltage pre-alarm

￿/￿

￿/￿

￿

￿

 

24

25

Main circuit undervoltage alarm

￿/￿

￿/￿

￿

￿

 

26

27

Low current alarm

￿/￿

￿/￿

￿

￿

 

28

29

Overtorque alarm

￿/￿

￿/￿

￿

￿

 

30

31

Braking resistor overload pre-alarm

￿/￿

￿/￿

￿

￿

 

32

33

In emergency stop

￿/￿

￿/￿

￿

￿

 

34

35

In course of retry

￿/￿

￿/￿

￿

￿

 

36

37

Pattern operation switching output

￿/￿

-

￿

￿

 

38

39

PID deviation limit

￿/￿

-

￿

￿

7.2.2

40

41

Run/Stop

￿/￿

￿/￿

￿

￿

 

42

43

Serious failure (OCA, OCL, EF, phase failure, etc.)

￿/￿

￿/￿

￿

￿

 

44

45

Light failure (OL, OC1, 2, 3, OP)

￿/￿

￿/￿

￿

￿

 

46

47

Commercial/INV switching output 1 (for inverter

￿/￿

-

￿

￿

 

operation output)

 

 

 

 

 

 

 

 

48

49

Commercial/INV switching output 2 (for commercial

￿/￿

-

￿

￿

 

operation output)

 

 

 

 

 

 

 

 

50

51

Cooling fan ON/OFF

￿/￿

￿/￿

￿

￿

 

52

53

In Jog run

￿/￿

-

￿

￿

 

54

55

Panel operation/terminal board operation switching

￿/￿

￿/￿

￿

￿

 

56

57

Cumulative operation time alarm

￿/￿

￿/￿

￿

￿

 

58

59

PROFIBUS/DeviceNet/CC-Link communication error

￿/￿

￿/￿

￿

￿

 

60

61

Forward/reverse run

￿/￿

￿/￿

￿

￿

 

62

63

Ready for operation 1

￿/￿

￿/￿

￿

￿

 

64

65

Ready for operation 2

￿/￿

￿/￿

￿

￿

 

68

69

Braking release signal

￿/￿

-

￿

￿

 

70

71

In (pre-)alarm status

￿/￿

￿/￿

￿

￿

 

72

73

Forward speed limit (torque control)

-

￿/￿

-

-

 

74

75

Reverse speed limit (torque control)

-

￿/￿

-

-

 

11

E6581301!

Page 299
Image 299