! E6581301

L-1

12
12. Specifications

12.1 Models and their standard specifications

1) Standard specifications (small/medium capacity types)
Item Specification
Voltage class
200V class
Applicable motor (kW)
0.4 0.75 1.5 2.2 3.7/4.0 5.5 7.5 11 15 18.5 22 30 37 45
Applicable motor (HP)
0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60
Rating
Type VFAS1-
Form
2004PL2007PL 2015PL2022PL 2037PL2055PL2075PL 2110PM2150PM2185PM2220PM2300PM 2370PM 2450PM
Output capacity (kVA)
[Note 1]
1.1 1.8 3.0 4.2 6.7 10 13 21 25 29 34 46 55 67
Output current
(A) [Note 2]
3.0
(3.0)
4.8
(4.5)
8.0
(8.0)
11
(10.5)
17.5
(16.6)
27.5
(25.0)
33
(33)
54
(49)
66
(64)
75
(66)
88
(75)
120
(88)
144
(120)
176
(140)
Output voltage Three-phase 200V~240V (The maximum output voltage is equal to the input supply voltage.)
Overload
current rating 150%-1 minute, 165%-2 sec.
Electrical
braking
Dynamic
braking circuit Built-in dynamic braking drive circuit
Dynamic braking
resistor
An external braking resistor (optional)
!
Rating: Refer to 5.19.
Power
supply
Voltage-frequency
! ! ! ! ! ! ! ! ! Three-phase 200~240V-50/60Hz [Note 3]
Allowable
fluctuation Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method
(IEC60529) IP20 Enclosed type IP00 Open type [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
43 43 43 55 55 56 58 60 60
60 60 64 64 64
Color RAL7016
EMC filter Built-in
Basic filter (Not complies with the European EMC Directive)
DC reactor External DC reactor (option) Built-in
Item Specification
Voltage class
400V class
Applicable motor (kW)
0.75 1.5 2.2 3.7/4.0 5.5 7.5 11 15 18.5 22 30 37 45 55 75
Applicable motor (HP)
1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100
Rating
Type VFAS1-
Form 4007PL4015PL4022PL4037PL4055PL4075PL 4110PL4150PL4185PL 4220PL4300PL4370PL 4450PL4550PL4750PL
Output capacity (kVA)
[Note 1]
1.8 3.1 4.4 8.0 11 13 21 25 31 37 50 60 72 88 122
Output current
(A) [Note 2]
2.3
(2.3)
4.1
(4.0)
5.8
(4.6)
10.5
(8.6)
14.3
(13)
17.6
(17)
27.7
(25)
33
(32)
41
(37)
48
(38)
66
(53)
79
(60)
94
(75)
116
(93)
160
(120)
Output voltage Three-phase 380V~480V (The maximum output voltage is equal to the input supply voltage.)
Overload
current rating 150%-1 minute, 165%-2 sec.
Electrical
braking
Dynamic
braking circuit Built-in dynamic braking drive circuit
Dynamic braking
resistor
An external braking resistor (optional)
!
Rating: Refer to 5.19.
Power
supply
Voltage-frequenc
y
! ! ! ! ! ! ! ! ! ! ! ! ! ! ! Three-phase 380~480V-50/60Hz [Note 3]
Allowable
fluctuation Voltage + 10% - 15% [Note 4] Frequency ±5%
Protective method
(IEC60529) IP20 Enclosed type IP00 Open type [Note 5]
Cooling method Forced air-cooled
Cooling fan noise (dBA)
43 43 43 55 56 56 58 60 60 60 64 64 64 64 64
Color RAL7016
EMC filter Built-in
DC reactor External DC reactor (option) Built-in
Note 1: Capacity is calculated at 220V for the 200V models and at 440V for the 400V models.
Note 2: Rated output current when the PWM carrier frequency (parameter EH) i s 4kHz or less.
The values between parentheses refer to rated output currents when set to 12 kHz.
Refer to 1.4.4 ”Current reduction curve” for details.
Note 3: If you are using a 200V-15kW or 400V-2.2kW inverter and the ambient temperature i s 40°C or more,
decrease the PWM carrier frequency to 8kHz. Setting H to enables you to protect the overload
caused by ambient temperature described in page A-23.
An external power supply backup available (optional) (Type: CPS002Z)
Note 4: ±10% when the inverter is used continuously (load of 100%).
Note 5: HN models, 200V-18.5!45kW and 400V-22!75kW are IP20 enclo sed type.