E6581301

E-35

5
!
!
An example of setting when WXE=
Motor speed"
Time"
Input voltage
"
Deceleration stop"
• Even after the recovery from an input power failure, the motor continues slowing down to a stop. If the voltage in the
inverter main circuit falls below a certain level, however, control will be stopped and the motor will coast.
• The deceleration time varies according to the setting of H. In this case, the deceleration time refers to the
time elapsed before a motor running at HJ(maximum frequency) comes to a full stop.
• If the voltage in main circuit below H (Under voltage detection level ) at Non-stop control during power failure,
the motor will coast and inverter display is shown "UVQR¶(displayed al ternately)". And then, If recovery from
the input power failure, the motor continues coasting.
An example of setting when WXE= (when the function of receiving synchronized acce leration/deceleration
signals is assigned to the input terminal S1)
H (Input terminal function selection 5 (S1)) = (Synchronized accel eration/deceleration signal)
Motor speed"
Time
"
Synchronized
acceleration/decel
eration signal "
(S1 terminal) "
H
Inverter 1
"
H
Inverter 2
"
ON"
• If the parameters H, H are set for same acceleration and decelera tion time and if synchronized
acceleration/deceleration signals set using the input terminal functions ( , ! are used, multiple motors can be
stopped at about the same time or speed commands can be issued to them at ab out the same time.
• If a synchronized acceleration/deceleration signal is impressed, the syn chronized deceleration function decreases
the output frequency to 0Hz to decelerate the motor linearly within the ti me specified with H. (The S-pattern
operation function or the braking sequence cannot be used along with this function.)
When the motor comes to a full stop, the message “STOP” appears on the displ ay panel.
• If the synchronized acceleration/deceleration signal is canceled duri ng synchronized deceleration, the synchronized
acceleration function increases the output frequency to the frequency at the start of synchronized deceleration or to
the command frequency, whichever is lower, to accelerate the motor linearly within the time speci fied with H.
(The S-pattern operation function, the braking sequence or the auto-tuning f unction cannot be used along with this
function.)
When acceleration is started, the message “STOP” on the display panel disappears.
• If a forward/reverse switching command or a stop command is issued duri ng synchronized acceleration or
deceleration, synchronized acceleration or deceleration will be cancel ed.
An example of setting when WXE=
Synchronized deceleration if a synchronized acceleration/deceleratio n signal is impressed or if a power failure
occurs, or synchronized acceleration if the synchronized acceleration/de celeration signal is canceled.