10.4Application and functions of options

Separate type options shown below are prepared for the inverter VF-AS1

￿

 

 

(2) DC reactor

 

(200kW models and larger)

 

 

(DCL)

 

 

 

 

 

 

 

 

 

 

(4) Braking resistor

(4) Braking resistor/Braking unit

 

 

 

 

 

No-fuse

 

(3) EMC filter for CE

 

 

 

breaker

Magnetic

compliance

 

 

 

Power supply (MCCB)￿

contactor

 

 

 

motor

 

(MC)￿

 

 

 

 

 

 

N.F

VF-AS1

 

IM

 

(1) Input AC reactor

 

(5) Motor end surge voltage

 

 

suppression filter (for 400V

 

(ACL)￿

 

 

 

 

 

models only)

 

 

 

 

 

 

(6)Control power supply backup option￿

 

Sorts of separate-type options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

Option name

 

 

 

Function, purpose.

 

 

 

 

 

Input AC reactor

To be used for improvement of input power-factor of the inverter power source, for reducing

 

 

 

(ACL)

higher harmonic or suppressing external surge. The input reactor can be installed when the

 

 

 

 

power capacity is 500 kVA or more and it is 10 times or more as high as the inverter capacity

 

 

 

 

or there are some source distorted wave generation such as a thyristor, etc. and a high

 

 

(1)

 

capacity inverter connected with the same distribution system.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Effect

 

 

 

 

 

 

 

Type of

Power-factor

Harmonic suppression

 

External surge

 

 

 

 

 

 

reactor

improvement

200V, 3.7/4.0kW

Other

 

suppression

 

 

 

 

 

 

 

 

or less

combination

 

 

 

 

 

 

 

 

Input AC

Effective

Effective

Effective

 

Effective

 

 

 

 

DC reactor(DCL)

 

reactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC reactor

Very effective

Effective

Very effective

 

Not effective

 

 

 

 

 

The DC reactor is superior to the input AC reactor in power-factor improvement. For the

 

 

 

 

inverter system that is required to be high reliable, it is recommended to use the input AC

 

 

(2)

 

reactor that effectually suppresses external surge together with the DC reactor.

 

 

 

200V/11 to 45kW models and 400V/18.5 to 75kW models come with a built-in DC rector as

 

 

 

 

 

 

 

 

standard equipment.

 

 

 

 

 

 

 

 

 

* If you are using a 200V/55kW model or larger or a 400V/90kW model or larger, be sure to

 

 

 

 

connect a DC reactor. (No DC reactor is required when the inverter is powered from a DC

 

 

 

 

power supply.)

 

 

 

 

 

 

 

 

 

EMC Directive

If EMC filter is installed in proper connection, the inverter has consistency with EMC

 

10

(3)

compliant noise

commands. 200V/0.4kW to 200V/7.5kW models and 400V/0.75 to 400V/500kW models come

 

 

reduction filter

standard with built-in noise filters. The effectiveness of the built-in filter can, however, be

 

 

 

(EMF3-*****)

increased by adding an EMC filter.

 

 

 

 

 

 

 

 

Braking resistor

To be used to shorten deceleration time for the reason of frequently operated quick

 

 

(4)

Braking unit

deceleration and suspension or high inertia load. This increases consumption of

 

 

 

regenerative energy in dynamic braking. !

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For 200kW more inverter, it requires the braking unit.

 

 

 

 

 

Motor end surge voltage

In a system in which 400 V class general motor is driven by a voltage PWM type inverter

 

 

 

suppression filter

using a high-speed switching device (IGBT, etc.), surge voltage depending on cable constant

 

 

(5)

(for 400 V models only)

may cause deterioration in insulation of motor winding. Take measures against surge voltage

 

 

 

 

such as use of insulation-reinforced motor, installation of AC reactor, surge voltage

 

 

 

 

suppression filter, sine wave filter and so on in the inverter’s output side.

 

 

 

 

 

 

Note) Set the carrier frequency to 4.0~8.0kHz when sine wave filter is used.

 

 

 

Control power supply

The VF-AS1 supplies control power from the main circuit power supply in it. The optional

 

 

 

backup option

backup unit is designed to supply control power in the event the main circuit power supply

 

 

(6)

 

shuts down.

 

 

 

 

 

 

 

 

 

 

The optional backup unit can be used with both 200V and 400V models.

 

 

 

 

 

 

Unit type: CPS002Z

 

 

 

 

 

 

 

J-5