E6581301

Output terminal function (open collector, relay outputs) setting and detection levels

For the open connector output terminals (OUT1, OUT2) and the relay output terminals (FLA, FLB and FLC), functions can be selected from 0 to 255 functions. The selectable functions and detection levels are listed in the table below.

Up to 7 output terminals can be used if add-on options are used in combination with the inverter, while up to 3 output terminals can be used if no add-on option is used.

<Technical terms>

• Alarm

·······Alarm output beyond a certain setting value.

Pre-alarm

·······Alarm output of the state where the inverter may carry out a trip by continuation.

• Serious failure

·······Output signal in a serious failure of the protection function of the inverter.

 

(Arm overcurrent (￿￿￿￿, ￿, ￿), Load side overcurrent (￿￿￿), Short-circuiting

 

(￿￿￿, ￿￿￿), Phase failure (￿￿￿￿, ￿￿￿￿), Abnormal output current detection

 

(￿￿￿￿))

• Light failure

·······Output signal in a slight failure of the protection function of the inverter.

 

(Overload (￿￿￿,￿), overvoltage (￿￿￿, ￿, ￿), overcurrent during

 

acceleration/deceleration/fixed speed operation (￿￿￿, ￿￿, ￿, ￿￿, ￿, ￿￿))

Emergency stop ·······Output signal when the inverter comes into emergency stop. Stopping manner is set with ￿￿￿￿ (emergency stop).

Table of output terminal functions and detection levels

 

 

Parameter setting

 

 

 

 

Positive

Negative

Function

Operation output specifications (in case of positive logic)

 

 

logic

logic

 

 

 

 

 

 

Lower limit frequency

ON:The running frequency is equal to or higher than the setting

 

 

￿￿

￿￿

of ￿￿ (Lower limit frequency)

 

 

(LL)

 

 

 

 

OFF:The running frequency is lower than the setting of ￿￿.

 

 

 

 

 

 

 

 

 

Upper limit frequency

ON:The running frequency is equal to or higher than the setting

 

 

￿￿

￿￿

of ￿￿ (Upper limit frequency)

7

 

(UL)

 

 

 

OFF:The running frequency is lower than the setting of ￿￿.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON:The running frequency is equal to or higher than the setting

 

 

￿￿

￿￿

Low-speed signal

of ￿￿￿￿ (low-speed signal output frequency)

 

 

 

 

 

 

OFF:The running frequency is lower than the setting of ￿￿￿￿.

 

 

 

 

Acceleration/decelerati

ON:The difference between the frequency command and the

 

 

￿￿

￿￿

running frequency is within the setting of ￿￿￿￿.

 

 

on completion

 

 

 

 

OFF:In acceleration or deceleration.

 

 

 

 

 

 

 

 

 

 

ON:The running frequency is in the range of ￿￿￿￿ ± ￿￿￿￿.

 

 

￿￿

￿￿

Speed reach signal

OFF:The running frequency is out of the range of ￿￿￿￿ ±

 

 

 

 

 

￿￿￿￿.

 

 

￿￿￿

￿￿￿

Failure FL

ON:Inverter is tripped.

 

 

(All trips)

OFF:Inverter trip is canceled.

 

 

 

 

 

 

￿￿￿

￿￿￿

Failure FL

ON:Inverter is tripped (except ￿￿ and ￿￿￿)

 

 

(Except EF, OCL)

OFF:Inverter trip is canceled. (reset)

 

 

 

 

 

 

 

 

Overcurrent (OC)

ON:Inverter output current is over the ￿￿￿￿ (Stall prevention

 

 

￿￿￿

￿￿￿

level) set value.

 

 

pre-alarm

 

 

 

 

OFF:Inverter output current is under the ￿￿￿￿.

 

 

 

 

 

 

 

 

 

Inverter overload

ON:A certain rate of inverter overload (￿￿￿) detection time is

 

 

￿￿￿

￿￿￿

over.

 

 

(OL1) pre-alarm

 

 

 

 

OFF:The detection time is within a certain limit.

 

 

 

 

 

 

 

 

 

Motor overload (OL2)

ON:A certain rate of inverter overload (￿￿￿) detection time is

 

 

￿￿￿

￿￿￿

over.

 

 

pre-alarm

 

 

 

 

OFF:The detection time is within a certain limit.

 

 

 

 

 

 

 

 

 

 

ON:The temperature of the cooling fin is 95°C or hi gher inside

 

 

￿￿￿

￿￿￿

Overheat pre-alarm

the inverter.

 

 

OFF:The temperature drops to 90°C or lower after ov erheat

 

 

 

 

 

 

 

 

 

 

pre-alarm was on.

 

 

 

 

 

Overvoltage control operation or PB operation in progress. ON:

 

 

￿￿￿

￿￿￿

Overvoltage pre-alarm

PB operation level + 3%

 

 

 

 

 

(200V class: Approx. 370Vdc, 400V class :Approx. 740Vdc)

 

 

 

 

Undervoltage in main

ON:The main circuit voltage is lower than the main circuit

 

 

￿￿￿

￿￿￿

circuit (MOFF)

undervoltage detection (￿￿￿￿) level.

 

 

 

 

detection

(200V class: Approx. 170Vdc, 400V class: Approx. 340Vdc)

 

 

￿￿￿

￿￿￿

Low current detection

ON: The state that inverter output current is ￿￿￿￿ set value

 

 

or larger continued more than ￿￿￿￿ set value.

 

 

 

 

 

G-6