5.2Setting acceleration/deceleration time

￿￿￿￿￿: Automatic acceleration/deceleration

￿￿￿￿￿: Acceleration time 1

￿￿￿￿￿: Deceleration time 1

Function

1)For acceleration time 1 ￿￿￿ programs the time that it takes for the inverter output frequency to go from 0Hz to maximum frequency ￿￿.

2)For deceleration time 1 ￿￿￿ programs the time that it takes for the inverter output frequency to got from maximum frequency ￿￿ to 0Hz.

5.2.1Automatic acceleration/deceleration

This automatically adjusts acceleration and deceleration time in line with load size.

￿￿￿=￿

*Adjusts the acceleration/deceleration time automatically within the range of 1/8 to 8 times as long as the time set with the ￿￿￿ or ￿￿￿, depending on the current rating of the inverter.

￿￿￿=￿

*Automatically adjusts speed during acceleration only. During deceleration, speed is not adjusted automatically but reduced at the rate set with ￿￿￿.

5

Output

When load is small

Output

 

frequency [Hz]

frequency [Hz]

 

 

 

 

￿￿￿

 

 

￿￿

 

0

 

 

0

 

 

 

 

Time [s]

 

 

Acceleration

Deceleration

 

When load is large

 

 

Time [s]

Acceleration

Deceleration

Acceleration/deceleration time decrease

Acceleration/deceleration time increase

Set ￿￿￿ (automatic acceleration/deceleration) to ￿ or ￿.

[Parameter setting]

Title

Function

Adjustment range

Default setting

 

 

￿:Disabled (Manual setting)

 

￿￿￿￿

Automatic acceleration/deceleration

￿:Automatic setting

￿

 

 

￿:Automatic setting (during

 

 

 

acceleration only)

 

!When automatically setting acceleration/deceleration time, always change the acceleration/deceleration time so that it conforms with the load.

The acceleration/deceleration time changes constantly with load fluctuations.

For inverters that requires a fixed acceleration/deceleration time, use the manual settings (￿￿￿, ￿￿￿).

!When using a braking resistor or braking unit, do not set the ￿￿￿=￿. Or the regenerative braking resistor may be overloaded.

!Use this parameter after actually connecting the motor.

!Setting acceleration/deceleration time (￿￿￿, ￿￿￿) in conformance with mean load allows optimum setting that conforms to further changes in load.

!When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or deceleration time in time, and therefore may be tripped.