< 3VT

14

VERTICAL TERMINATION

when (HT) > (VT)

Simple venting configurations

See graph to determine the required vertical rise VT for the

FIGURE 11

Formula 2: HT + VT < 40 feet 15.9 < 40

Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration will need to be established to satisfy both formulas.

Example 5:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V2

 

 

 

 

 

 

 

 

 

 

 

90°

 

 

 

 

required horizontal run HT.

 

 

 

 

 

45°

 

 

H2

 

H3

90°

For vent configurations requiring more than one 45º and one

 

 

H1

 

V1

45°

90° elbow , the following formulas apply:

 

 

 

 

 

 

 

 

 

19

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REQUIRED

 

 

 

 

 

 

 

 

 

 

 

90°

 

FIGURE 13

 

VERTICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

R I S E I N

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FEET (VT)

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

V1

 

=1.5 ft

 

 

 

 

 

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

V2

 

=8 ft

 

 

 

 

 

VT

 

= V1

+ V2 = 1.5 + 8= 9.5 ft

 

 

The shaded area within the lines represents acceptable

 

 

 

H1

 

=1 ft

 

 

 

 

values for HT

and VT.

< 3VT

 

 

 

 

 

H2

 

=1 ft

 

 

 

 

Formula 1: HT

 

 

 

 

 

H3

 

=10.75 ft

 

 

 

 

Formula 2: HT + VT < 40 feet

 

 

 

HR

 

= H1

 

+ H2

+ H3

= 1 + 1 + 10.75 = 12.75 ft

 

Example 4:

 

 

 

 

 

 

HO

 

= .03(three 90° elbows + two 45° elbow - 135°)

 

 

 

 

 

 

 

 

= .03(90 + 90 + 90 + 45 + 45 - 135) = 6.75 ft

V1

=1 ft

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HT

 

=HR

+ HO = 12.75 + 6.75 = 19.5 ft

 

FIGURE 12

 

 

 

 

 

 

 

HT

+ VT

= 19.5 + 4.5= 29 ft

 

 

 

 

 

 

 

 

 

 

 

Formula 1:

HT < 3VT

 

 

 

45°

 

 

 

 

 

 

 

 

 

 

 

3VT

= 3 x 9.5 = 28.5 ft

 

 

 

 

 

 

 

 

 

 

 

19.5 < 28.5

 

 

 

 

90°

 

V2

 

 

H1

H2

 

 

 

V1

90°

 

 

 

 

 

 

 

9

 

V2

 

=1.5 ft

 

 

VT

 

= V1 + V2 = 1 + 1.5 = 2.5 ft

 

 

H1

 

=6 ft

 

 

H2

 

=2 ft

 

 

HR

 

= H1 + H2 = 6 + 2 = 8 ft

 

 

HO

 

= .03(one 45º elbow + three 90º elbow - 135º)

 

 

= .03(45 + 90 + 90 + 90 - 135) = 5.4 ft

HT

+ VT

=HR + HO = 8 + 5.4 = 13.4 ft

 

HT

= 13.4 + 2.5 = 15.9 ft

 

 

Formula 1: HT < 3VT

3VT = 3 x 2.5 = 7.5 ft

13.4 > 7.5

Since this formula is not met, this vent configuration is unacceptable.

Formula 2: HT + VT < 40 feet 29 < 40

Since both formulas are met, this vent configuration is acceptable.

W415-0547 / B / 05.08.06

Page 14
Image 14
Napoleon Fireplaces GDS25N GDS25P manual Vertical Termination, 3VT, Formula 1 HT, Formula 2 HT + VT 40 feet