Napoleon Fireplaces GDS 50-N Gas Installation, B-VENTMODEL GS50 ONLY, DIRECT VENT MODEL GDS50

Models: GDS 50-P GDS 50-N

1 24
Download 24 pages 47.44 Kb
Page 14
Image 14
GAS INSTALLATION
FIGURE 31

14

GAS INSTALLATION

GAS INSTALLATION

 

B-VENT MODEL GS50 ONLY

Read the section on opening the door in "Finish- ing" prior to proceeding to prevent damaging the unit.

Bring the gas line to the stove through either the opening in the pedestal back or through the floor directly beneath the pedestal base.

Install rigid black pipe or ½" type L copper tubing with a shut-off valve to the stove.

Seal and tighten the gas line securely to the flex connector supplied.

Do not kink the flexible connector.

Mark the two appropriate boxes on the rating plate la- bel. One to indicate the model type depending on the in- stallation (direct vent or B-vent). Mark the second box to indicate the altitude type and the type of fuel being used (natural gas or propane).

CERTIFIEDUNDERCSA2.33A-M98,ANSIZ21.88A-1998

HOMOLOGUESELONLESNORMESFOYERDECHAUFFAGE

VENTEDGASFIREPLACEHEATERAPPLIANCEMUSTBE

AU GAZ AVEC EVACUATION CET APPAREIL DOIT ETRE

INSTALLED USING BURNER KIT : GDS50BN-KT,

INSTALLE EN UTILISANT UN ENSEMBLE DU BRULEUR:

OR GDS50BP-KT.

 

 

GDS50BN-KT,OUGDS50BP-KT.

CDVS500 -N

GDS50 -N

 

GDS50-P

CDVS500 -P

CS500-N

GS50-N

 

 

GS50-P

CS500-P

0-2000ft (0-610m)

2000-4500ft (610-1370m) ALTITUDE/ELEVATION

40,000 BTU/h

2000-4500ft (610-1370m)

44,000 BTU/h

40,000 BTU/h

 

INPUT/ALIMENTATION

21,000 BTU/h

36,000 BTU/h

20,000 BTU/h

18,000 BTU/h

REDUCED INPUT / ALIMENTATION REDUITE30,400 BTU/h

18,000 BTU/h

33,000 BTU/h

30,000 BTU/h

 

OUTPUT (MODEL GDS50) RENDEMENT 30,000 BTU/h

27,400 BTU/h

31,200 BTU/h

28,400 BTU/h

 

OUTPUT (MODEL GS50) RENDEMENT

#53

26,400 BTU/h

#34

#36

 

FRONT ORIFICE / INJECTEUR AVANT

#57

#53

#43

#45

 

TURBO ORIFICE / INJECTEUR TURBO

 

#59

 

 

 

 

Attach one lead from the spill switch (white wire) to terminal #3 located on the gas valve and the other (black) on/off switch lead to valve terminal #1.

FIGURE 30

Attach the B-Vent label, shown below, in the control area of the appliance.

ATTACH THIS LABEL IN THE CONTROL AREA OF THE FIREPLACE.

THIS FIREPLACE HAS BEEN CONVERTED TO A ‘B’VENT MODEL.

ATTACHEZ CET ETIQUETTE DANS LA REGION DE CONTROLE DU FOYER.

CE FOYER AETE CONVERTI AUN MODELE ASYSTEME D’EVACUATION ‘B’.

ws-385-160

Check for gas leaks by brushing on a soap and water solu- tion. DO NOT USE OPEN FLAME.

DIRECT VENT MODEL GDS50

Disconnect the existing wires from terminals 1 and 3 (from the on/off switch) and replace with the leads from the wall switch/millivolt thermostat.

B-VENT MODEL GS50

*ALTITUDEDOWNRATINGCONDITIONSAPPLYTOCANADA ONLY

LES CONDITIONS DE BAISSE D’EVALUATION SELON L’ALTITUDES’APPLIQUENTAUCANADASEULEMENT MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG) / 10 INCHES W.C.(LP) PRESSION AU COLLECTEUR: 3.5" D'UNE COLONNE D'EAU(GN)

10" D'UNE COLONNE D'EAU (PG)

MIN SUPPLY PRESSURE: 4.5" W.C.(NG) / 11" W.C. (LP)

PRESSIOND'ALIMENTATIONMIN:4.5"D'UNECOLONNED'EAU

11" D'UNE COLONNE D'EAU (PG)

MAX. SUPPLY PRESSURE: 7" W.C. (NG) / 13" W.C. (LP)

PRESSIOND'ALIMENTATIONMAX:7"D'UNECOLONNED'EAU

13" D'UNE COLONNE D'EAU (PG)

FOR USE WITH GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.

UTILISER AVEC LES PORTES VITREES HOMOLOGUEES SEULEMENTAVECCETTEUNITE.

WARNING:DONOTADDANYMATERIALTOTHEAPPLIANCE, WHICHWILLCOMEINCONTACTWITHTHEFLAMES,OTHER THANTHATSUPPLIEDBYTHEMANUFACTURERWITHTHEAP- PLIANCE.

AVERTISSEMENT: N'AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT.

MINIMUMCLEARANCETOCOMBUSTIBLEMATERIAL/ DEGAGEMENTSMINIMAUXDESMATERIAUXCOMBUSTIBLES:

A

7"

D 17½"

B

2"

E 6¼"

C

1"

F 9½"

20"TOCEILINGFROMSTOVETOP B-VENT MODEL GS50 ONLYDo not kink the flexible connector.DIRECT VENT MODEL GDS50B-VENT MODEL GS50 20"ENTRELEDESSUSDUFOYERETLEPLAFOND ELECTRICAL RATING / CLASS.: 115V 1.5AMP 60HZ

B-VENT MODELS GS50/CS500 APPROVED FOR BED-

ROOM,&BEDSITTINGROOMINSTALLATION. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, & UN STUDIO.

STEADY STATE EFFICIENCY (NG): 71% FAN OFF / 77% FAN ON

STEADY STATE EFFICIENCY (LP): 73% FAN OFF / 78% FAN ON

EFFICACITECONSTANTE(GN):71%VENT.ARRETE 77%VENT.FONCTIONNE

EFFICACITECONSTANTE(GP):73%VENTILATEURARRETE 78% VENTILATEUR FONCTIONNE STEADY STATE EFFICIENCY APPLIES TO CANADA ONLY /

L'EFFICACITE CONSTANTE S'APPLIQUENT SEULEMENT AU CANADA.

AFUE (NG/LP) (GN/GP): 64% / 67%

THISAPPLIANCEMUSTBEINSTALLEDUSINGANADAPTER KITGS-150KT.CETAPPAREILDOITETREINSTALLEENUTILI- SANTUNENSEMBLEADAPTATEURGS-150KT.

NOT FOR USE WITH SOLID FUEL

UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE

AVEC CET APPAREIL

DIRECT VENT MODELS GDS50 CDVS500 APPROVED FOR BEDROOM, BATHROOM & BEDSITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT APPLI- CABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS, SITES AND COM- MUNITIES, ANSI / NFPA 501A.

HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON IN- STALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.

STEADY STATE EFFICIENCY (NG):75% FAN OFF / 78% FAN ON

STEADYSTATEEFFICIENCY(LP):76% FAN OFF / 79% FAN ON

EFFICACITE CONSTANTE (GN): 75% VENT. ARRETE

78% VENT. FONCTIONNE

EFFICACITE CONSTANTE (GP): 76% VENTILATEUR ARRETE 79%VENTILATEURFONCTIONNE STEADY STATE EFFICIENCY APPLIES TO CANADA ONLY /

L'EFFICACITE CONSTANTE S'APPLIQUENT SEULEMENT AU CANADA.

AFUE (NG/LP) (GN/GP): 65% / 67%

MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 25 INCHES AND 20 FEET RESPECTIVELY. LES LONGUEURS HORIZONTALES MINIMALE ET MAXIMALE SONT 25 POUCES ET 20 PIEDS RESPECTIVEMENT.

THE APPLIANCE MUST BE VENTED USING THE APPROPRI- ATE NAPOLEON VENT KITS. SEE OWNERS INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLA- TION AND RESEALING IS NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.

L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A NAPOLEON. REFERER AU MANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL EST IMPORTANT DE BIEN REINSTALLER ET RESCELLER L'EVENT APRES AVOIR AS- SURE LE MAINTIEN DU SYSTEME DE PRISE D'AIR.

WOLF STEEL LTD

BARRIE, ONTARIO CANADA

MADE IN CANADA / FABRIQUE AU CANADA

SERIALNUMBER GDS50

NO.DESERIE

WS-385-181

Disconnect the existing on/off switch wire from terminal 1 on the valve and the black switch wire from the terminal block. Replace each connection using the wires from the wall switch/millivolt thermostat. FIGURE 30.

FIGURE 29

W415-0098 / C / 04.19.06

Page 14
Image 14
Napoleon Fireplaces GDS 50-N, GDS 50-P manual Gas Installation, B-VENTMODEL GS50 ONLY, DIRECT VENT MODEL GDS50