FP-PS-4Operating Instructions 8 ni.com
6. Connectthe green or green/yellow conductor into the ground
terminal.
Caution Whenyou install the conductors, make sure that
theentire conductor is in the screw terminal and that there
areno loose strand so utside of the terminal. Only install
onewire in each terminal.
SpecificationsThefollowing specifications are typical for a range of 0 to 60 °C,
unlessotherwise noted.
Installation
Terminalwiring ................................16-26 AWG copper
conductorwire with 7 mm
(0.275in.) strip length as
showninFigure8
Figure8. ConductorWirewiththeCorrectStripLength(drawingistoscale)
Torquefor screwterminals ...............0.5-0.6 Nm(4.4 –5.3 in.-lbs)
Input Characteristics
Inputvoltage .....................................90–264 VAC
Frequency.................. ....................... 47–63 Hz, single phase
Maximumcurrent consumption........ 0.6 A at 120 VAC,60 Hz
Inputprotection ................................. N onreplaceable internal
AC fuse
OutputCharacteristics
Outputvoltage ..................................24 VDC,nonadjusting
Nominalcurrent (IN) ................. ........ 600 mA
Nominalcontinuous power
0to50°C..... .............................. 15 W
50to 60 °C ................................. 10 W
7mm