FP-PS-4Operating Instructions 8 ni.com
6. Connectthe green or green/yellow conductor into the ground
terminal.
Caution Whenyou install the conductors, make sure that
theentire conductor is in the screw terminal and that there
areno loose strand so utside of the terminal. Only install
onewire in each terminal.
Specifications
Thefollowing specifications are typical for a range of 0 to 60 °C,
unlessotherwise noted.

Installation

Terminalwiring ................................16-26 AWG copper
conductorwire with 7 mm
(0.275in.) strip length as
showninFigure8
Figure8. ConductorWirewiththeCorrectStripLength(drawingistoscale)
Torquefor screwterminals ...............0.5-0.6 Nm(4.4 5.3 in.-lbs)

Input Characteristics

Inputvoltage .....................................90264 VAC
Frequency.................. ....................... 4763 Hz, single phase
Maximumcurrent consumption........ 0.6 A at 120 VAC,60 Hz
Inputprotection ................................. N onreplaceable internal
AC fuse

OutputCharacteristics

Outputvoltage ..................................24 VDC,nonadjusting
Nominalcurrent (IN) ................. ........ 600 mA
Nominalcontinuous power
0to50°C..... .............................. 15 W
50to 60 °C ................................. 10 W
7mm