Chapter 4 Connecting Signals
NI 6115/6120 User Manual 4-28 ni.com
Either the 20MHz or 100 kHz internal timebase generates SISOURCE
unless you select some external source. Figure4-22 shows the timing
requirements for SISOURCE.
Figure 4-22. SISOURCE Signal Timing
SCANCLK SignalSCANCLK is an output-only signal that generates a pulse with the leading
edge occurring approximately 50 to 100ns after an A/D conversion begins.
The polarity of this output is software-selectable but is typically configured
so that a low-to-high leading edge can clock external AImultiplexers
indicating when the input signal has been sampled and can be removed.
This signal has a 450 ns pulse width and is software enabled.
Note When using NI-DAQ, SCANCLK polarity is low-to-high and cannot be changed
programmatically.
Figure4-23 shows the timing for SCANCLK.
Figure 4-23. SCANCLK Signal Timing
tp = 50 ns minimum
tw = 23 ns minimum
twtw
tp
td = 50 to 100 ns
tw = 450 ns
td
CONVERT*
SCANCLK tw