© National Instruments Corporation 27 NI cDAQ-9172 User Guide and Specifications
Digital I/OTo use digital I/O, insert a digital C Series I/O module into any slot on
the NI cDAQ-9172 chassis. The I/O specifications, such as number of lines,
logic levels, update rate, and line direction, are determined by the type
of C Series I/O module used. For more information, refer to the
documentation included with your C Series I/O modules.
Correlated vs. Static DIO Modules
Digital I/O module capabilities are determined by the type of digital signals
that the module is capable of measuring or generating. Static Digital I/O
modules are designed for signals that change slowly and are accessed by
software-timed reads and writes. Correlated Digital I/O modules are
for signals that change rapidly and are updated by either software or
hardware-timed reads and writes. Correlated Digital I/O modules can
perform the following tasks:
• Used in any slot—software-timed reads and writes.
• Used in slots 1 though 4—Digital Waveform Generation and
Acquisition (Correlated Input/Output)
• Used in slots 5 and 6—Counter/Timer
• Used in slots 5 and 6—Access PFI signals
To determine the capability of digital I/O modules supported by the
NIcDAQ-9172 chassis, refer to the KnowledgeBase document,
C Series Modules Supported in the NI cDAQ-9172. To access this
KnowledgeBase document, go to ni.com/info and enter the info code
rdcdaq.
Available features, such as trigger and counter/timer, are determined by the
slot containing the digital C Series I/O module and the capabilities of the
module.
Table 3. Digital Module Slot Features
Slots Static DIO PFI1Counter/Timer1
Digital
Waveform/Change
Detection1
1Yes — — Yes
2Yes — — Yes
3Yes — — Yes
4Yes — — Yes