New Buck Corporation 32 manual Gas Pressure Check

Models: 32

1 42
Download 42 pages 39.82 Kb
Page 20
Image 20
GAS PRESSURE CHECK

GAS PRESSURE CHECK

Check the inlet pressure to the burner to ensure that it is shown in the table below.

NOTE: The pressure check point is located on the right side of the valve facing burner, for SIT Millivolt, and the left side for SIT Modulating.

The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2

psi (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its equipment shut -off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).

VALVE

(MILLIVOLT)

(SIT MANUAL-MODULATING)

MODEL:

FP32

FP32

FP32

FP32

GAS

Natural

Propane

Natural

Propane

Maximum Heat Input

33,000

33,000

33,000

33,000

Minimum Heat Input

23,000

23,000

12,000

13,000

Gas Inlet Pressure

 

 

 

 

Maximum

10.5ins.W.C.

13ins.W.C.

10.5ins.W.C.

9.0ins.W.C.

Minimum

* 5.0ins.W.C.

*11ins.W.C.

*5.0ins.W.C.

*11ins.W.C.

Manifold Pressure

 

 

 

 

Maximum

3.5ins.W.C.

9.0ins.W.C.

3.5ins.W.C.

9.0ins.W.C.

Minimum

3.0ins.W.C.

8.2ins.W.C.

2.8ins.W.C.

7.2ins.W.C.

NOTE: On initial installation it may be necessary to bleed out air in the gas lines. Do this by holding the control knob and turning the knob to the “PILOT” position for about 30 seconds. To check the regulator pressure, remove the pressure tag plug at the left side of the regulator facing the heater. The pressure should be checked with the heater burning and the control set on high. After measuring the pressure, replace the pressure tap plug, ensuring that there are no leaks.

* For the purpose of minimum input adjustment.

Solid fuels shall not be burned in the same fireplace where an unvented room heater has been installed.

NOTE: The following label has been provided with this appliance and must be read and then attached to the floor of the fireplace or firebox area beneath the appliance. The label is a peel and stick label. Make sure the area is cleaned before attaching the label to it.