![Figure 12](/images/new-backgrounds/55034/5503457x1.webp)
RAIN CAP | Figure 12 |
|
24" min. |
|
(610 mm) | 36" TYP. |
| FLASHING |
| RADIATION SHIELD |
| 20 FT. MAX. |
OUTSIDEAIRAIRDUCTDUCTTHROUGHTHROUGHFLOOR WHENFLOOR WHENMOBLE HOMEMOBILEIS NOTISUNOTDERPEUNDERPINNED
RAIN CAP
24" min. |
|
(610 mm) | 36" TYP. |
FLASHING
RADIATION SHIELD |
OUTSIDEAIRAIRDUCTDUCTTHROUGHTHROUGHUNDERPENNEDUNDERPINNING
Ceiling Exit (Using Close Clearance Listed Chimney)
1.Suspend a plumb bob from ceiling above unit so that weight is hanging in center of flue exit. (A small weight on a string will serve as a plumb bob). Mark ceiling where string is suspended to locate center of chimney hole.
2.After locating center of hole, install ceiling support box, chimney or chimney connector, flashing and rain cap using listed 2100° HT chimney only. Only use pipe listed in this manual.
3.Add additional pipe until both of the following are met:
Page 27