Nordyne R-410A General Information, Outdoor Unit, Liquid and Suction Lines, Inspect for Damage

Models: R-410A

1 20
Download 20 pages 19.69 Kb
Page 7
Image 7
GENERAL INFORMATION

GENERAL INFORMATION

Split System Heat Pump units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations equipped with variable speed blowers.

This unit has been designed and tested for capacity and effi ciency in accordance with A.R.I. Standards. This unit will provide many years of safe and dependable comfort, providing it is properly installed and maintained. With regular maintenance, this unit will operate satisfactorily year after year. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.

To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.

Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit.

Outdoor Unit

Each outdoor unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler.These units include the proper amount of refrigerant for an additional 15 ft. of refrigerant lines the same size as the valve fi ttings.

NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.

Matching coils and air handlers may be shipped with a small holding charge to pressurize them to keep out contaminants.To release the pressure, read the indoor section installation instructions carefully.

Liquid and Suction Lines

Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.

Field Connections for Electrical Power Supply All wiring must comply with current provisions of the “National Electrical Code” (ANSI/NFPA

70)and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.

SITE PREPARATION

Unpacking the Equipment

Remove the shipping carton and User’s Manual from the equipment.Take care not to damage the tubing connections when removing the carton.

Inspect for Damage

Inspect the equipment for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove fl attened or bent fi ns.

Preferred Location of the Outdoor Unit Survey the job site to determine the best location for mounting the outdoor unit.Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit.

Facility Prerequisites

Electrical power supplied to the unit must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes.

Minimum Circuit Ampacity

Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.

Maximum Fuse / Circuit Breaker Size Circuit protection for the outdoor unit must be compatible with the maximum fuse/circuit breaker size listed on the outdoor unit data label.

INSTALLING THE INDOOR UNIT

The indoor unit (air handler, furnace, etc.) should be installed prior to the routing of refrigerant piping. Consult the Installation Instructions of the indoor unit for installation details.

INSTALLING THE OUTDOOR UNIT

Slab Mount

The site selected for a slab mount installation requires a stable foundation and not subject to erosion. The slab should be level and anchored (if necessary) prior to installation on the slab.

Cantilever Mount

The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment.

7

Page 7
Image 7
Nordyne R-410A General Information, Outdoor Unit, Liquid and Suction Lines, SITE PREPARATION Unpacking the Equipment