•Connect the
•Use only copper wire for the line voltage power supply to this unit (Table 1). Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
•See the unit wiring label for proper high and low voltage wiring.Make all electrical connections in accordance with all applicable codes and ordinances.
•Use a separate branch electrical circuit for this unit.A means of electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically
•Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes.
Outdoor Unit Connections
The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram / schematic for identifi cation and location of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring
The outdoor unit is designed to operate from a 24 VAC Class II control circuit.The control circuit wiring must comply with the current provisions of the NEC (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
Thermostat Connections
Thermostat connections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment. A typical residential installation with a heat pump thermostat and air handler are shown in Figure 2.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire | Supply Circuit | |||
200 | 150 | 100 | 50 | Ampacity |
|
|
|
|
|
6 | 8 | 10 | 14 | 15 |
4 | 6 | 8 | 12 | 20 |
4 | 6 | 8 | 10 | 25 |
4 | 4 | 6 | 10 | 30 |
3 | 4 | 6 | 8 | 35 |
3 | 4 | 6 | 8 | 40 |
2 | 3 | 4 | 6 | 45 |
2 | 3 | 4 | 6 | 50 |
2 | 3 | 4 | 6 | 55 |
1 | 2 | 3 | 4 | 60 |
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
Grounding
CAUTION:
The unit must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur.This ground may consist of electrical wire or approved conduit when installed in accordance with national or local codes.
Low-Pressure Switch
A
If the suction pressure falls below 5 psig, the switch will open and
High-Pressure Switch
A
|
| Thermostat |
|
NOTE: Jumper | G | R W2 C E O Y1 Y2 W1 W3 |
|
W1 & W2 together |
|
|
|
for shorter staging |
|
|
|
time. |
|
|
|
Y1 |
|
|
|
W2 |
|
| R |
W1 |
| W2 |
|
|
| OD | |
|
|
| |
O |
| E | Stat |
| C O Y1 Y2 | ||
|
| ||
Y/Y2 |
|
|
|
G |
|
|
|
R |
|
|
|
C |
|
|
|
Air Handler |
| Heat Pump OD Section |
Figure 2. Typical 2 - Stage Heat Pump w/ Optional Outdoor Thermostat and Variable Speed Air Handler
9