TROUBLESHOOTING - CONTINUED
Miswired Module Indication |
| Recommended Troubleshooting Action | |||
Green LED is not on, module | • Determine if both R & C module terminals are connected. | ||||
does not power up | • | Verify voltage is present at module’s R & C terminals. | |||
|
|
|
|
| |
Green | LED | intermittent, | • | Determine if R & Y terminals are wired in reverse. | |
module powers up only when | |||||
• Verify modules R and C terminals have a constant source. | |||||
compressor runs |
| ||||
|
|
| |||
|
|
|
|
| |
|
|
| • | Verify Y terminal is connected to 24VAC at contactor coil. | |
Trip LED is on, but system and | • | Verify voltage at contactor coil falls below 0.5VAC when | |||
| off. | ||||
compressor check OK |
| ||||
• Verify 24VAC is present across Y & C when thermostat | |||||
|
|
| |||
|
|
|
| demand signal is present. If not, R & C are reversed wired. | |
|
|
|
| ||
TRIP LED and | ALERT LED | • | Verify R and C terminals are supplied with 19 - 28VAC. | ||
fl ashing together |
| ||||
|
|
| |||
|
| ||||
ALERT Flash CODE 3 displayed | • Verify Y terminal is connected to 24VAC at contactor coil. | ||||
incorrectly | (Compressor short | • | Verify voltage at contactor coil falls below 0.5VAC when | ||
cycling) |
|
|
| off. |
•Verify the compressor run and start wires are routed
ALERT Flash Code 5, 6, or 7 through the module’s current sensing holes.
displayed incorrectly (Open | • | Verify the Y terminal is connected to 24VAC at contactor | |
Circuit, Open Start Circuit or |
| coil. | |
Open Run Circuit) | • | Verify voltage at contactor coil falls below 0.5VAC when | |
|
| off. | |
|
|
| |
ALERT Flash Code 6 (Open |
|
| |
Start Circuit) displayed for | • | Verify the compressor run and start wires are routed | |
Code 7 (Open Run Circuit) or |
| through the correct module sensing holes. | |
|
| ||
|
|
| |
| • | Determine if module’s Y terminal is connected. | |
| • | Verify Y terminal is connected to 24VAC at contactor coil. | |
| • Verify 24VAC is present across Y & C when thermostat | ||
ALERT Flash Code 8 displayed |
| demand signal is present. If not, R and C are reversed | |
| wired. | ||
incorrectly (Welded Contactor) |
| ||
• | Verify voltage at contactor coil falls below 0.5VAC when | ||
| |||
|
| off. | |
| • Review Thermostat Demand Wiring (page 10) for Y & C | ||
|
| wiring. | |
| |||
Table 5. Module Wiring Troubleshooting |