INSTALLATION INSTRUCTIONS
READ & SAVE THESE INSTRUCTIONS!
Ultra-QuieTTest Fan/Lights
MODELS: LS80L, LS100L
SUITABLE FOR USE OVER TUB OR SHOWER ENCLOSURE
WHEN INSTALLED IN A GFCI PROTECTED BRANCH CIRCUIT.
ROOF CAP
IMPORTANT SAFETY INSTRUCTIONS | 4" DIAMETER DUCT | |
WARNING: TO REDUCE THE RISK OF FIRE. ELECTRIC SHOCK, | ||
| ||
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: |
| |
A. Use this unit only in the manner intended by the manufacturer. |
| |
If you have questions, contact the manufacturer. |
| |
B. Before servicing or cleaning unit, switch power off at service | 90° ELBOW | |
panel and lock service panel to prevent power from being | ||
WALL CAP | ||
switched on accidentally. | ||
| ||
When the service disconnecting means cannot be locked, securely |
| |
fasten a prominent warning device, such as a tag, to the service panel. |
| |
CAUTION: |
| |
For general ventilating use only. Do not use to exhaust hazardous |
| |
or explosive materials and vapors. |
| |
INSTALLATION INSTRUCTIONS | CEILING INSTALLATION |
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, |
|
|
| FIGURE 1 | |
OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: |
|
|
| ||
|
|
|
| ||
A. Installation work and electrical wiring must be done by qualified |
|
|
|
| |
person(s) in accordance with all applicable codes and standards, including |
|
|
|
| |
construction. |
|
|
|
| |
B. Sufficient air is needed for proper combustion and exhausting of gases through the |
|
|
|
| |
flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating |
|
| LAMP |
| |
equipment manufacturer's guideline and safety standards such as those published by | FAN |
|
| ||
| RECEPTACLE | GROUND | |||
the National Fire Protection Association (NFPA),and the American Society for | RECEPTACLE | ||||
(3 PIN) | |||||
Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), |
|
| SCREW | ||
|
|
| |||
and the local code authorities. |
|
|
|
| |
C. When cutting or drilling into wall or ceiling, do not damage electrical wiring |
|
|
|
| |
and other hidden utilities. |
|
|
|
| |
D. Ducted fans must always be vented to the outdoors. |
|
|
|
| |
E. If this unit is to be installed over a tub or shower, it must be marked as appropriate for |
|
|
|
| |
the application and be connected to a GFCI (Ground Fault Circuit Interrupter) |
|
|
|
| |
protected branch circuit. |
|
|
|
| |
F. NEVER place a switch where it can be reached from a tub or shower. |
|
|
|
| |
• Do not install in a ceiling insulated to a value greater than R40. |
|
|
|
| |
• Suitable for use with solid state speed controls. Use NuTone Model |
|
|
|
| |
• Not for use in kitchens. |
|
|
| SWITCH BOX | |
FOR BEST RESULTS |
|
|
| ||
|
|
|
| ||
When installing the Ventilator in a new construction site, install housing during | (NEUTRAL)WHITE | (HOT)BLACK |
|
| |
the |
|
| |||
|
|
|
| ||
after the finished ceiling is in place. |
|
|
|
| |
To install a ventilator in an existing building requires an accessible area (attic or |
|
|
|
| |
crawl space) above the planned location. |
|
|
|
| |
INSTALLATION IN A NEW CONSTRUCTION SITE |
|
|
|
|
PREPARATION | 120v AC SUPPLY |
1.Remove blower/power unit assembly from housing:
A.If necessary, unplug power unit.
B.Loosen one (1) mounting screw.
C.Slide unit back to free it from the mounting screw.
D.Remove unit and set aside until needed.
2. Remove wiring knockouts from housing, as needed. | FIGURE 2 |