Operating Parameters

FTB600B Series

2

Operating Parameters

Section 2. - Operating Parameters

A. Temperature

Since the FTB600B Series has printed circuit boards molded into the body of the meter it is strongly recommended that 180°F not be exceeded. Exceeding 180°F can cause irreparable damage to the circuit boards.

B. Flow Ranges

The FTB600B Series is available in six different sizes, which cover a flow range from 0.1 to 120 lpm.

Specific flow ranges

FTB601B

0.1 to 2 lpm

(0.03 to 0.53 gpm)

FTB602B

0.3 to 9 lpm

(0.08 to 2.38 gpm)

FTB603B

0.5 to 15 lpm

(0.13 to 3.96 gpm)

FTB604B

1.0 to 30 lpm

(0.26 to 7.93 gpm)

FTB605B

2.5 to 75 lpm

(0.66 to 19.8 gpm)

FTB606B

4.0 to 120 lpm

(1.32 to 32 gpm)

 

 

 

 

 

 

 

 

 

 

WARNING

 

 

 

 

 

 

 

Over range may permanently damage the flow meter.