4.3.7.5 Analog Output Retransmission
This menu will appear only if you have the Analog Output Option installed in your Meter.
SETUP
Address http://192.168.1.200
SETUP
Analog Output Retransmission
Retransmission
Voltage/Current
Input Low
Output Low
Input High
Output High
Enabled
Voltage
0
0.00 Min. 0V
100
10.00 Max. 10V
Update
Cancel
Main Menu
Figure 4.18 Analog Output Retransmission Retransmission: When enabled, the input data will be scaled based on Input Low and Input High and will be outputted. When disabled, the output will be acting as On/Off. If the input reaches low value the output will be 10V and 20mA. If the input reaches high value, the output will be 0V and 0mA. Voltage/Current: Select the output to be Voltage (0-10V) or Current (0-20mA). Input Low: The minimum input value scaled for Output Low.
Output Low: Output Voltage or Current represented by Input Low.
Input High: The minimum input value scaled for Output High.
Output High: Output Voltage or Current represented by Input High.
46