Chimney height requirements:

NOTES:

1.Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through system and the chimney wall, to but not past the inner flue liner face.

2.A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.

Chimney height requirements:

The chimney must extend 3 feet above the level of roof penetration and a minimum of 2 feet higher than any roof surface within 10 feet. Check with your local building officials for additional requirements for your area.

The condition of the chimney and height is very important; we suggest a total minimum height of 15’ (4,5m). Measured From the floor level on which the stove is installed.