Open access cover on the overload, then set the overload amperage dial to match the FLA amperage of your motor. The FLA value can be found on your motor nameplate.

Overload

Amperage

Dial

Be sure you have the proper voltage available for your Starter’s Power & Control Circuit (Control circuit controls Contactor Coil in Starter). Coil voltage is/can be independent from the line voltage that runs your motor. Customers may desire an alternative Contactor Coil voltage to connect a Starter to a low voltage control circuit. Most OAS Starters are shipped with 240v coils.

Plug the Start/Stop Push-Button Assembly into keyed receptacle. (As shown below.)

Run power to the starter and from the starter to your motor. See the manufacturer instructions for more details.

The Power Circuit connected to the Starter should be fed from a dedicated circuit breaker or disconnect with fuses. Don’t connect any branch circuits to the Mag Starter Power Circuit. The overcurrent protection (circuit breaker or fuse*) for the Starter Power Circuit is to be sized per Article 430.32 of the NEC.

*Use time delay fuses rated for motor circuits.

 