Bat Tmp Err The battery temperature sensor is shorted or damaged.

EQ 0:00 This is the time elapsed in hours and minutes since the Equalization voltage was met. If the EQ voltage set point is not maintained, the controller will revert back to EQ-MPPT – the EQ timer will pause until the batteries are regulated at the EQ target again. The paused time can be viewed in the Log2 menu.

EQ DONE Once the set EQ time, (between 1 and 7 hours), has successfully completed, EQ DONE will be displayed either until a button is pressed, or the next morning’s wakeup. The MX60 will tran- sition to Float cycle at the end of the EQ cycle.

EQ-MPPT The equalization process has started and the MX60 is trying to regulate towards the Equalization voltage set point. EQ is not battery temperature compensated. After the EQ voltage has been reached, EQ 0:00 will be displayed along with the EQ time in hours and minutes. The AC/DC loads should be turned off and the battery should be charged so the MX60 can reach the EQ voltage set point. Otherwise, the MX60 may not reach or maintain the EQ cycle.

Float The MX60 is in the Float charge stage and is regulating the battery at the Float voltage set point. If the system cannot keep up with the Float voltage set point, (e.g. AC and/or DC loads are on), the MX60 will employ the MPPT function, display F-MPPT, and try its best to regulate the bat- teries to the Float set point.

F-MPPT The MX60 is in Maximum Power Point Tracking mode trying to regulate the battery volt- age towards the Float voltage set point. Note: Charge Timer (ChgT) is inactive in the Float state.

GT Mode In a system with an OutBack FX G-series Inverter/Charger, HUB and MATE, the MX60 will display GT Mode if and only if the inverter is in Sell mode and the MX60 is in Bulk (B-MPPT) or Float (F-MPPT) cycle. This is also a good indicator for establishing proper Grid tie mode communication between the FX G-Series Inverter(s) and MX60.

High Voc This indicates the PV array’s open circuit voltage is too high for the controller to safely operate. This should only occur with systems using 72 VDC nominal PV arrays in very cold tem- peratures (below 50 F / -150 C). The controller will automatically restart operation once the PV array’s open circuit voltage falls to a safe level (141 VDC). The amount of time required to reset is dependent on the module type, ambient temperature, and the amount of sunlight directly on the PV array. Normally, the controller starts in the morning within a few minutes of the PV array being in direct sunlight.

68

OutBack Power Systems Inc.

Page 68
Image 68
Outback Power Systems MX60 user manual OutBack Power Systems Inc

MX60 specifications

The Outback Power Systems MX60 is a state-of-the-art solar charge controller designed for off-grid and grid-tied systems, providing users with cutting-edge technology and efficiency in managing their solar energy resources. This device stands out in the renewable energy market due to its versatile features, robust performance, and ease of use.

One of the main features of the MX60 is its high-efficiency MPPT (Maximum Power Point Tracking) technology. This advanced technology optimizes the energy harvested from solar panels by adjusting the electrical operating point of the modules, allowing the system to extract the maximum available power. The MX60 can handle a considerable input voltage of up to 150 volts and offers a maximum output current of 60 amps, making it suitable for both small and large-scale installations.

The MX60’s robust architecture ensures its durability in harsh environmental conditions. With an operating temperature range of -40°F to 176°F, the charge controller performs reliably in varied climatic conditions, whether in extreme heat or bitter cold. This makes it an ideal choice for remote locations and rugged terrains where traditional power sources might be unreliable or unavailable.

An intuitive LCD interface equipped with a user-friendly display allows for easy monitoring and configuration. Users can track real-time performance metrics, including solar array voltage, output current, battery voltage, and charging status. The device is also equipped with advanced programmable settings, offering users complete control over charging parameters and battery maintenance.

Moreover, the MX60 incorporates essential safety features, including over-voltage and over-current protection, reverse polarity protection, and temperature compensation. Such safety measures are crucial in preventing damages to both the controller and the connected battery system.

The MX60 is compatible with various battery types, including Flooded, AGM, Gel, and Lithium, providing flexibility in energy storage options. It seamlessly integrates with Outback's Radian inverter systems, facilitating a comprehensive energy management solution for residential and commercial applications.

In summary, the Outback Power Systems MX60 is an exceptional choice for those looking for a reliable and efficient solar charge controller. Its combination of advanced technology, robust construction, and user-friendly features makes it an essential component for anyone interested in harnessing the power of solar energy.