Panasonic CU-S18NKU-1, CS-S18NKU-1, CS-S12NKUW-1 10.2 S18NKU-1 S22NKU-1, Select the Best Location

Models: CS-S9NKUW-1 CS-S22NKU-1 CU-S18NKU-1 CS-S18NKU-1 CS-S12NKUW-1 CU-S22NKU-1 CU-S12NKU-1 CU-S9NKU-1

1 103
Download 103 pages 8.8 Kb
Page 39
Image 39

10.2S18NKU-1 S22NKU-1

10.2.1Select the Best Location

10.2.1.1Indoor Unit

Do not install the unit in excessive oil fume areas such as kitchens, workshops etc.

There should not be any heat source or steam near the unit.

There should not be any obstacles blocking the air circulation.

A place where air circulation in the room is good.

A place where drainage can be easily done.

A place where noise prevention is taken into consideration.

Do not install the unit near a doorway.

Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.

Recommended installation height for indoor unit shall be at least 8.2 ft.

10.2.1.2Outdoor Unit

If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.

There should not be any animal or plant which could be affected by hot air discharged.

Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.

Do not place any obstacles which may cause a short circuit of the discharged air.

If piping length is over the [piping length for additional gas], additional refrigerant should be added as shown in the table.

Recommended installation height for outdoor unit should be above the seasonal snow level.

Example: For S18NKU-1

If the unit is installed at 41 ft distance, the quantity of additional refrigerant should be 1.64 oz .... (41 - 32.8)

ft x 0.2 oz/ft = 1.64 oz.

10.2.2Indoor/Outdoor Unit Installation Diagram

39

Page 39
Image 39
Panasonic CU-S18NKU-1, CS-S18NKU-1, CS-S12NKUW-1, CS-S22NKU-1, CS-S9NKUW-1 10.2 S18NKU-1 S22NKU-1, Select the Best Location