14.1.1Relationship between the condition of the air conditioner and pressure and electric current

Condition of the

 

Cooling Mode

 

air conditioner

Low Pressure

High Pressure

Electric current during operation

 

 

 

 

Insufficient refrigerant

Ô

Ô

Ô

(gas leakage)

 

 

 

Clogged capillary tube or

Ô

Ô

Ô

strainer

 

 

 

Short circuit in the indoor unit

Ô

Ô

Ô

 

 

 

 

Heat radiation deficiency

Ò

Ò

Ò

of the outdoor unit

 

 

 

Inefficient compression

Ò

Ô

Ô

 

 

 

 

• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.