Panasonic CU-2S18NBU-1 Evacuation Of The Equipment, Connect The Cable To The Outdoor Unit

Models: CU-2S18NBU-1

1 43
Download 43 pages 32.39 Kb
Page 18
Image 18
10.4 EVACUATION OF THE EQUIPMENT

10.4 EVACUATION OF THE EQUIPMENT

WHEN INSTALLING AN AIR CONDITIONER, BE

SURE TO EVACUATE THE AIR INSIDE THE

INDOOR UNIT AND PIPES in the following procedure.

1.Connect a charging hose with a push pin to the Low side of a charging set and the service port of the gas side 3-way valve.

2.Connect the micron gauge between vacuum pump and service port of outdoor units.

3.Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and to pull down to a value of 500 microns.

4.To make sure micron gauge a value 500 microns and close the low side valve of the charging set and turn off the vacuum pump.

5.Disconnect the vacuum pump house from the service port of the 3-way valve.

6.Tighten the service port caps of gas side 3-way valve at a torque of 13.3 Ibf.ft with a torque wrench.

7.Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open” using a hexagonal wrench (5/32").

8.Mount valve caps onto the 2-way valve and 3- way valve.

Be sure to check for gas leakage.

10.5 CONNECT THE CABLE TO THE OUTDOOR UNIT CAUTION

If micron gauge value does not descend 500 microns, take the following measures:

oIf the leak stops when the piping connections are tightened further, continue working from step e. o If the leak does not stop when the connections are retightened, repair location of leak.

o Do not release refrigerant during piping work for installation and reinstallation. o Take care when handling the liquid refrigerant, it may cause frostbite.

10.5 CONNECT THE CABLE TO THE OUTDOOR UNIT

1.Remove Control Board Cover (Metal) by loosening 2 screws.

2.Remove Valve Cover (Metal) by loosening 2 screws.

3.Remove Plugs.

4.Fix the conduit connectors to the knock out holes with lock-nuts, then secure them.

5.Connecting wire between indoor unit and outdoor unit should be UL listed or CSA approved 4 conductor wires minimum AWG16 in accordance with local electric codes.

6.Wire Connection to the power supply (208/230V 60Hz) through circuit breaker.

Connect the UL listed or CSA approved wires minimum AWG12 to the terminal board, and connect to other end of the wires to circuit

breaker.

7.Connect the power supply cord and connecting wires between indoor unit and outdoor unit according to the diagram as shown.

18

Page 18
Image 18
Panasonic CU-2S18NBU-1 service manual Evacuation Of The Equipment, Connect The Cable To The Outdoor Unit