Diagnosis | Abnormality |
|
|
|
|
|
|
|
|
|
| |
or | LED | LED | LED | LED | LED | LED | Abnormality | Protection | Problem | Check location | ||
display | Protection | 6 | 5 | 4 | 3 | 2 | 1 | Judgment | Operation | |||
|
| |||||||||||
| control |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Indoor high | • Check indoor heat | |
| Indoor high |
|
|
|
|
|
|
|
| exchanger | ||
|
|
| ○ | ○ | ○ |
| ― | ― | pressure | |||
H98 | pressure |
|
|
| • Air filter dirty | |||||||
|
|
| protection | |||||||||
| protection |
|
|
|
|
|
|
|
| (Heating) | • Air circulation | |
|
|
|
|
|
|
|
|
|
| short circuit | ||
|
|
|
|
|
|
|
|
|
|
| ||
| Indoor |
|
|
|
|
|
|
|
|
| • Check indoor heat | |
|
|
|
|
|
|
|
|
| Indoor freeze | exchanger | ||
| operating unit |
|
| ○ | ○ | ○ |
|
|
| |||
H99 |
|
|
| ― | ― | protection | • Air filter dirty | |||||
freeze |
|
|
| |||||||||
| protection |
|
|
|
|
|
|
|
| (Cooling) | • Air circulation | |
|
|
|
|
|
|
|
|
|
| short circuit | ||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| ○ | ○ | ○ | ○ | 4 times |
| • | |||
F11 | switching |
|
| happen within | ― | Switching | • Lead wire and | |||||
| abnormality |
|
|
|
|
|
| 30 minutes |
| abnormal | connector | |
|
|
|
|
|
|
|
|
|
|
| • Check indoor/ | |
|
|
|
|
|
|
|
|
|
|
| outdoor | |
|
|
|
|
|
|
|
|
|
| Wrong wiring and | connection wire | |
|
|
|
|
|
|
|
|
|
| and pipe | ||
| Indoor standby |
|
|
|
|
|
| 3 times |
| connecting pipe, | ||
|
|
|
|
|
|
|
| • Indoor heat | ||||
|
| ○ |
|
|
|
|
| expansion valve | ||||
F17 | units freezing |
|
|
|
|
| happen within | ― | exchanger sensor | |||
|
|
|
|
| leakage, indoor | |||||||
| abnormality |
|
|
|
|
|
| 40 minutes |
| heat exchanger | lead wire and | |
|
|
|
|
|
|
|
|
|
| connector | ||
|
|
|
|
|
|
|
|
|
| sensor open circuit | ||
|
|
|
|
|
|
|
|
|
| • Expansion valve | ||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| lead wire and | |
|
|
|
|
|
|
|
|
|
|
| connector | |
| Power factor |
|
|
|
|
|
| 4 times |
| Power factor |
| |
| correction |
| ○ |
|
|
| ○ |
| • Outdoor PCB | |||
F90 |
|
|
|
| happen within | ― | correction circuit | |||||
(PFC) circuit |
|
|
|
| faulty | |||||||
| protection |
|
|
|
|
|
| 10 minutes |
| abnormal |
| |
|
|
|
|
|
|
|
|
|
|
| ||
| Refrigeration |
| ○ |
|
| ○ |
| 2 times |
| Refrigeration | • Insufficient | |
F91 | cycle |
|
|
|
| happen within | ― | refrigerant or valve | ||||
|
|
|
| cycle abnormal | ||||||||
| abnormality |
|
|
|
|
|
| 20 minutes |
|
| close | |
| Compressor |
| ○ |
|
| ○ | ○ | 4 times |
| Compressor | • Power transistor | |
F93 | abnormal |
|
|
| happen within | ― | abnormal | module faulty or | ||||
| revolution |
|
|
|
|
|
| 20 minutes |
| revolution | compressor lock | |
| Compressor |
|
|
|
|
|
| 4 times |
| Compressor |
| |
| discharge |
| ○ |
| ○ |
|
|
| • Check | |||
F94 | pressure |
|
|
|
| happen within | ― | discharge pressure | refrigeration | |||
| overshoot |
|
|
|
|
|
| 30 minutes |
| overshoot | system | |
| protection |
|
|
|
|
|
|
|
|
|
| |
| Outdoor cooling |
|
|
|
|
|
| 4 times |
| Cooling high | • Check | |
|
| ○ |
| ○ |
| ○ |
| refrigeration | ||||
F95 | high pressure |
|
|
| happen within | ― | pressure | |||||
|
|
| system | |||||||||
| protection |
|
|
|
|
|
| 20 minutes |
| protection | • Outdoor air circuit | |
|
|
|
|
|
|
|
|
|
|
| ||
| Power transistor |
|
|
|
|
|
| 4 times |
| Power transistor | • PCB faulty | |
F96 | module |
| ○ |
| ○ | ○ |
| ― | ||||
|
|
| happen within | • Outdoor air circuit | ||||||||
overheating |
|
|
| module overheat | ||||||||
| protection |
|
|
|
|
|
| 30 minutes |
|
| (fan motor) | |
|
|
|
|
|
|
|
|
|
|
| ||
| Compressor |
| ○ |
| ○ | ○ | ○ | 3 times |
| Compressor | • Insufficient | |
F97 | overheating |
|
| happen within | ― | |||||||
|
| overheat | refrigerant | |||||||||
| protection |
|
|
|
|
|
| 30 minutes |
|
|
| |
| Total running |
|
|
|
|
|
| 3 times |
|
| • Check | |
|
| ○ | ○ |
|
|
|
| Total current | refrigeration | |||
F98 | current |
|
|
|
| happen within | ― | system | ||||
|
|
|
| protection | ||||||||
| protection |
|
|
|
|
|
| 20 minutes |
|
| • Power source or | |
|
|
|
|
|
|
|
|
|
|
| compressor lock | |
| Outdoor direct |
| ○ | ○ |
|
| ○ | Continuous |
| Power transistor | • Power transistor | |
F99 | current (DC) |
|
|
| happen for 7 | ― | module current | module faulty or | ||||
| peak detection |
|
|
|
|
|
| times |
| protection | compressor lock |
LED 1 illuminate is indicated that outdoor unit is operating normally. If the LED 1 is switched off or flashing, check the power supply and
●