FP-X series

Great expandability

Only 1 E16 can be connected serially.

E16 can be sandwiched with E30*

C60

E16

E16

C60

NG

Connection by using the cable included with each expansion unit.

C60

 

E30

 

E30

 

 

 

 

 

 

 

 

 

 

An 80-cm expansion cable is

Note: Total expansion

also available as an option.

cable length: 160cm max.

E16

OK

E30

*E30 requires an external power supply

The units can be mounted very close to each other with the cable bent inside between the units in order to save space.

When further expansion or functions are required, use the existing FP0 expansion units

All control units can be expanded by up to 3 FP0 expansion units via an adapter. Applications can be expanded by using [Transistor outputs], [analog input/outputs], [thermocouple input] and [I/O link (network)].

C60

E30

E30

Max. 7 units (210 points)

Max. 96 points

 

* Only 1 expansion FP0 adapter unit can be attached to a control unit.

 

Expansion FP0 adapter

Up to 7 FP-X expansion units can be used when the expansion FP0 adapter is attached.

(AFPX-EFP0)*

In addition to the supplied 8cm expansion cable, 30cm and 80cm tpyes are available as options, allowing the units to be arranged more freely. (Total expansion cable length: 160cm max.)

Product number

Specifications

 

 

FP0-E8X

8ch. DC input, MIL connector

 

 

FP0-E16X

16ch. DC input, MIL connector

 

 

FP0-E8YT/-E8YP

8ch. transistor output, MIL connector

 

 

FP0-E8YRS

8ch. relay output, screw terminal block

 

 

FP0-E16YT/-

16ch. transistor output, MIL connector

E16YP

 

 

 

FP0-E32T/-E32P

16ch. DC input, 16ch. transistor output,

MIL connector

 

 

 

FP0-E8RS

4ch. DC input, 4ch. relay output,

screw terminal block

 

 

 

FP0-E16RS

8ch. DC input, 8ch. relay output,

screw terminal block

 

 

 

FP0-E32RS

16ch DC input,

16ch relay output screw terminal block

 

 

 

Product number

Specifications

 

 

FP0-A21

Analog 2ch. input, 1ch. output

 

 

FP0-A80

Analog 8ch. input

 

 

FP0-A04V

Analog (voltage) 4ch. output

 

 

FP0-A04I

Analog (current) 4ch. output

 

 

FP0-TC4

Thermocouple 4ch. input

 

 

FP0-TC8

Thermocouple 8ch. input

 

 

FP0-RTD6

6ch RTD input

 

 

FP0-IOL

I/O link unit

 

 

FP0-CCL

CC-link unit

 

 

FP0-DPS2

PROFIBUS remote I/O unit

 

 

We also have other units.

Please refer to the part number list at the end of this catalog.

The panel surface look clean due to the uniform unit height of 90mm.

01/2008

Page 7
Image 7
Panasonic FP-X Series manual Great expandability, Product number Specifications