FP-X series

Specifications

Control specifications

Item

Specifications

 

Program method

Relay symbol method

 

Control method

 

Cyclic operation method

 

Program memory

Flash ROM built-in (no battery backup required)

 

 

 

 

 

Program capacity

16k steps (C14), 32k steps (C30, C60)

 

 

 

 

 

Operation processing speed

Basic instruction 0.32Μs/step

 

 

 

 

 

Basic instructions

111

 

 

 

 

 

Applied instructions

216

 

 

 

 

 

External inputs (X)

1760 points *1

 

External outputs (Y)

1760 points *1

 

Internal relay (R)

4096 points

 

 

 

 

 

Special internal relay (R)

192 points

 

 

 

 

 

 

Link relay (L)

 

2048 points

 

 

 

 

 

 

Timer/counter (T/C)

Total 1024 points: timer capable of counting

 

(1ms, 10ms, 100ms, 1s) x 32767

 

 

 

 

Counter capable of counting 1 to 32767

 

 

 

 

 

Data register (DT)

12285 words (C14), 32765 words (C30, C60)

 

 

 

 

 

Link data register (LD)

256 words

 

 

 

 

 

Special data register (DT)

374 words

 

Index register (I0 to ID)

14 words

 

 

 

 

 

Master control relay (MCR)

256 points

 

 

 

 

 

Number of labels (LOOP)

256 labels

 

 

 

 

 

Number of differentiations

Up to program capacity

 

Number of stepladders

1000 stages

 

 

 

 

 

Number of subroutines

500 subroutines

 

 

 

 

 

 

Number of interruption programs

Relay output type: 15 programs (14 external, 1 constant)

 

Transistor output type: 9 programs (8 external, 1 constant)

 

 

 

 

 

 

 

 

 

 

 

 

 

Built-in (Transistor output): single-phase 8ch (50kHz x 4ch + 10kHz x 4ch)

 

High-speed counter *2

Built-in (Relay output): single-phase 8ch (10kHz x 8ch)

 

 

 

 

Pulse I/O cassette: single-phase 2ch (80kHz x 2ch)

 

 

 

 

 

 

Pulse output *3

 

Built-in (Transistor output): 100kHz x 2ch + 20kHz x 2ch

 

 

 

 

Pulse I/O cassette: One unit (one axis) 100kHz, or two units (two axes) 80kHz

 

Pulse catch input / interrupt input

Relay output type: Total 14 points (including the high-speed counter)

 

Transistor output type: Total 8 points (including the high-speed counter)

 

 

 

 

 

Periodical interrupt

0.5ms to 30s

 

Potentiometer

 

2 points (0 to 1000) (C14, C30) 4 points (0 to 1000) (C60)

 

Constant scan

 

Possible

 

Real-time clock

 

Equipped (usable only when AFPX-MRTC is installed) *4

 

Flash ROM

 

Backup by F12,

Data register (32,765 words)

 

 

P13 commands

 

backup *6

 

 

 

 

Auto-backup

Counter 16 points (1008 to 1023), Internal relay 128 points

 

 

 

at power failure

(R2470 to R255F), Data register 55 words

 

Battery backup

 

The memory allocated in the storage area by the

 

 

system register (only when a battery is installed) *5

 

 

 

Before installing

C14: 1230 days (actual operation 10 years at 25°C)

 

 

 

AFPX-MRTC

C30, C60: 990 days (actual operation 10 years at 25°C)

 

Battery life

 

After installing

C14: 780 days (actual operation 10 years at 25°C)

 

(when no power

 

AFPX-MRTC

C30, C60: 680 days (actual operation 10 years at 25°C)

 

is supplied)

 

 

(More than two batteries can be installed in C30 and C60.

 

 

 

 

In this case, the battery life is extended several times)

 

 

 

 

 

 

Password

 

Capable (4 or 8 characters selectable)

 

 

 

 

 

Self-diagnosis function

Watch dog timer, program syntaxcheck

 

 

 

 

 

Comment storage

Capable (328KB) (backup battery not required)

 

 

 

 

 

 

PLC link function

Max. 16 units, link relay 1024 points, link register 128 words

 

(No data transfer or remote programming)

 

 

 

 

 

 

 

 

 

Rewriting in RUN mode

Capable

 

 

 

 

 

 

Notes:

*1 The actual usable number of points is restricted by the hardware.

*2 Specification at the rated input voltage of 24V DC, 25°C. Frequency may be lower due to the voltage and temperature.

*3 Max frequency may vary by the method of operation. Please refer to the manual for details.

*4 Calendar accuracy at 0°C: 119sec/month or less, 25°C: 51 sec/month or less, 55°C: 148 sec/month or less (Real-time clock requires a battery.)

*5 When data is stored in the storage area while the battery is not installed, the data is not cleared and the data value may be indefinite. The same condition occurs when the battery is exhausted. *6 The number of possible rewrites is 10,000 or less.

01/2008

21

Page 21
Image 21