Item Description

Rated voltage
Operating voltage range
Service power output
Rush current
Allowed momentary power off time
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Breakdown voltage
Insulation resistance
Vibration resistance
Shock resistance
Noise immunity
Operating condition
EC Directive Compliance Standard
Level of contamination
Over-voltage category
110ms or more
0 to +55°C
-40 to +70°C
10 to 95% RH (at 25°C, non-condensing)
10 to 95% RH (at 25°C, non-condensing)
100 to 240VAC (AC power), 24VDC (DC power)
85 to 264VAC (AC power), 20.4 to 28.8VDC (DC power)
C14: 24VDC/0.15A, C30 and C60: 24VDC/0.4A
Combined input/output terminals - Combined power and ground terminals,
2300VAC*1 1 minute (AC power), 500VAC*1 1 minute (DC power)
Input terminals - Relay output terminals, 2300VAC*1 1 minute
Input terminals - Transistor output terminals, 500VAC*1 1 minute
Power terminals - Ground terminals, 1500VAC*1 1 minute (AC power),
500VAC*1 1 minute (DC power)
Input terminals - Output terminals, 100M7 or higher (500VDC using an insulation resistance meter)
Power terminals - Ground terminals, 100M7 or higher (500VDC using an insulation resistance meter)
Combined input/output terminals - Combined power and ground terminals,
100M7 or higher (500VDC using an insulation resistance meter)
40A or less (C14), 45A or less (C30, C60) at 25°C (AC power)
12A or less at 25°C (DC power)
No corrosive gas and no excessive dust
Conforming to EN61131-2
2
II
1500V [P-P] pulse width 50ns, 1Ms (AC power),
500V [P-P] pulse width 50ns, 1Ms (DC power)
(per noise simulator method) (power terminals)
5 to 9Hz, single amplitude 3.5mm/9 to 150Hz, constant acceleration 9.8m/s2,
1 sweep/min, 10 sweeps in each XYZ direction
147m/s2, 4 times on 3 axes
Note:
*1 Cutoff current 5mA

WeightProduct name Part number

Current consumption

Control Unit
Expansion I/O Unit
Expansion FP0 adapter
Input cassette
Output cassette
Pulse I/O cassette
Master memory cassette
Analog input cassette
Analog I/O cassette
Analog output cassette
Thermocouple input cassette
AFPX-C14;;
AFPX-C30;;
AFPX-C60;;
AFPX-E16;;
AFPX-E30;;
AFPX-EFP0
AFPX-IN8
AFPX-TR8
AFPX-TR6P
AFPX-PLS
AFPX-MRTC
AFPX-AD2
AFPX-A21
AFPX-DA2
AFPX-TC2
26W or less*2
52W or less*2
64W or less*2
8W or less*2
45W or less*2
0.24W or less*3
1W or less*2
1W or less*2
1W or less*2
2W or less*2
2W or less*2
2W or less*2
3W or less*2
5W or less*2
1W or less*2
2W or less*2
3W or less*2
2W or less*2
Approx. 280g or less
Approx. 490g or less
Approx. 780g or less
Approx. 195g or less
Approx. 470g or less
Approx. 65g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 20g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 25g
Approx. 20g
Approx. 25g
Approx. 20g
Notes:
*2 Power consumption by the AC power supply connected to the control unit
*3 Power consumption by the DC power supply connected to the expansion FP0 adapter
Please refer to the user manual and specifications for further details.
Communication
cassettes
AFPX-COM1
AFPX-COM2
AFPX-COM3
AFPX-COM4
AFPX-COM5
AFPX-COM6

01/2008