Installation
2-53163-A2-GB20-10 March 1999
Installing the Redundant –48 Vdc PowerSupply
To install the DSU/CSU using a redundant –48 Vdc
power supply, refer to Figure 2-5 and use the following
procedure.
"Procedure
To install the redundant –48 Vdc power supply:
1. Connect the black wire to the –48 Vdc return
source B.
2. Connect the red wire to the –48 Vdc return
source A.
3. Connect the green wire to a suitable ground.
4. Connect the orange wire to the –48 Vdc input
source B.
5. Connect the blue wire to the –48 Vdc input
source A.
6. Cut the white wire off at the outer insulation.
7. Plug the power connector into the DSU/CSU.
1
2
3
4
5
6
BLACK
RED
GREEN
WHITE
ORANGE
BLUE
–48 VDC RETURN B
–48 VDC RETURN A
GROUND
–48 VDC INPUT B
–48 VDC INPUT A
99-14300-02
X
DSU/CSU POWER
PLUG TO CUSTOMER-SUPPLIED BATTERY
Figure 2-5. 48 Vdc Redundant Source Power Supply Pinouts