Specification Summary

Parameter

Specification

Power Requirements

 

Vo

User-supplied voltage that drives output circuitry.

 

Vo does not affect input circuitry, so it is not

 

necessary for the VM24-IN.

Vo Range

5-24VDC

Vo Current

144mA, plus the sum of the load currents outputs

 

that are in sourcing mode.

V i

User-supplied voltage that drives input circuitry &

 

determines switching levels for inputs. Does not

 

affect output circuitry, so it is not necessary for

 

the VM24-OUT.

Vi Range

5-24VDC

Vi Current

1.5mA per volt of Vi

 

(e.g., 15mA for Vi=10V)

+5V

Supplied by the 6000 Series Controller/Indexer

 

through the 50-pin ribbon cable to connector J4.

 

The VM24 draws 0.25mA per active output and

 

0.5mA per active input. Also provides the

 

+5V output power available through the

 

VM24 screw terminal block J5.

Inputs

Switching levels ....... LOW 1/3 (Vi )

HIGH 2/3 (Vi)

Voltage Range.......... 0-24V. Voltage of input signals should not

exceed voltage level of Vi. (Input circuitry of VM24 has diodes to protect against voltages that exceed Vi, but performance may degrade.)

Sinking Current:....... Connect jumper for desired socket to position 3

(default)

Sourcing Current: ..... Connect jumper for desired socket to position 1

4 VM24 I/O Module

Page 8
Image 8
Parker Hannifin vm24 manual Specification Summary, Parameter Specification