ELECTRICAL
6. ELECTRICAL
Install all electrical wiring in accordance with the National Electrical Code and local requirements.
NOTICE
This unit when installed must be electrically grounded in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the current edition of the National Electrical Code, ANSI/NFPA 70 and/or the Canadian Electrical Code, Part 1 CSA C22.1, Electrical Code.
A. WIRING | C. CONTROLS |
1.See Figure 6.1 for location of wiring and controls. Use Figures 6.2 and 6.3 to connect the boiler to a power supply and to connect components to the boiler.
2.Connect the boiler by a separate, permanently live electrical supply line with a fused switch.
3.Connect the vent damper harness to the damper motor as shown in Figure 6.1.
4.Adjust the thermostat heat anticipator to 0.2 Amp.
B.ZONED SYSTEM WIRING
See Figure 6.5 for typical wiring with zone valves. See Figure 6.6 for typical wiring with zone circulators. When wiring a zoned heating system, follow all applicable codes, ordinances and regulations.
NOTICE
Do not power zone valves directly from the boiler limit. Doing so will greatly reduce the life of the transformer. Use a separate transformer sized to handle the total of all zone valve electrical loads.
1.For proper location of controls and accessories refer to Figure 6.1 and Section 11.
2.See the attached control sheets for specific details regarding the installation of the various controls.
3.This boiler is supplied with safety devices in addition to the limit. For a description of these devices and how they work to ensure the safe operation of the boiler, see Section 7B.
4.If the circulator is mounted in the supply piping, provide longer wiring harness as required.
Figure 6.1: Wiring, Controls and Safety Devices
16