WATER PIPING AND CONTROLS

3. WATER PIPING AND CONTROLS

A.BOILER SUPPLY AND RETURN

1.Size the supply and return to suit the system. A typical piping arrangement is shown in Figure 3.1. Refer also to the I=B=R Guide - Residential Hydronic Heating Installation/Design and the PB Heat Water Survey for additional guidance during water piping installation.

2.Return Piping:

Pipe the drain valve to a tee, provided, and the

1-1/4 NPT return tapping near the bottom of the left section. Pipe the return to the tee. Pipe the drain valve nipples and tee to the 1-1/4 NPT return tapping as shown in Figure 3.1.

3.Supply Piping:

Pipe the supply to the 1-1/2 NPT supply tapping at the top and rear of the boiler.

4.When system return water temperature will be below 130°F (54°C), pipe the boiler with a bypass arrangement to blend the system return and hot supply to obtain at least 130°F (54°C) entering the boiler. For more information on bypass piping, consult the PB Heat Water Survey.

Figure 3.1: Supply and Return Piping

7