Section 1: Installing a mounting bracket and light fixture during new vinyl pool construction
D A N G E R !
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION
This Nicheless light fixture must be installed by a licensed or certified electrician or a qualified pool serviceman in accordance with the National Electrical Code and all applicable local codes and ordinances. Improper installation will create an electrical hazard which could result in death or serious injury to pool users, installers or others due to electrical shock and may also cause damage to property. Always disconnect power to the pool light at the circuit breaker before servicing the light. Failure to do so could result in death or serious injury to serviceman, pool users or others due to electrical shock.
A.Preparatory steps which must be completed by the electrician before light is installed, see Figure 1.
1.Be sure the electrical system of the pool conforms with the requirements of the current National Electrical Code (NEC) and all local codes and ordinances. A licensed or certified electrician must install the electrical system to meet or exceed those requirements before the Nicheless Light is installed. Some of the requirements of the NEC are listed below.
a.The lighting circuit must have a Ground Fault Circuit Interrupter (GFCI), and have an appropriately rated
circuit breaker.
AquaLumin II Replacement Parts
Part |
|
Item Number | Description |
1619601 Face ring (white)
619632 Face ring (black)
2 | 619797 | Lens |
3619599 Lens gasket
478889900 Captive screw
5* | 619584 | Halogen lamp 12 volt /100 watt |
| 619484 | Halogen lamp 120 volt / 250 watt |
6619792 Sealing screws (10 req.)
600140 Kwik change lens set (4) (not shown)
Note: (*) Sold in Bulb Replacement Kits 600139 and 600138.
b.The junction box (or, for 12 volt models, the low voltage transformer) is located at least 12 inches above water level, and at least 48 inches from the edge of the pool, see Figure 1.
c.The light fixture and all metal items within five
(5) feet of the pool must be properly electrically bonded.
TO GFCI, CIRCUIT | 48" | |
MIN. | ||
BREAKER AND | ||
| ||
POWER SOURCE |
| |
RIGID CONDUIT |
| |
TO EXISTING |
| |
BONDING |
| |
CONNECTOR |
| |
MOUNTING HUB |
|
Figure 1
12" MIN. FROM BOTTOM OF JUNCTION BOX OR LOW VOLTAGE TRANSFORMER TO WATER LINE
WATER
LEVEL
18" MIN. FROM WATER TO TOP OF FACE RING