SCADA 3000 User’s Manual

How the Annunciator Module Works

The Annunciator module appears as an output module to the SCADA 3000. When the system is powered up, the main unit will scan the external module network and add the Annunciator to its list of modules at the address specified by the Bus Address jumpers. An icon for the Annun- ciator will also appear on the main unit screen.

The Annunciator module provides eight LED indicators which can be used to display the status of I/O points, system variables, or alarm conditions. The LEDs can be forced on (Red) or off (Amber) through the Annunciator module programming screen, or they may be controlled automatically using a C-program or Ladder program. The eight LEDs appear in the program- ming software as digital outputs numbered from 0-7. To access the Annunciator programming screen, click on the Annunciator icon from the Main Unit form or select Modules, then Annun- ciator, from the main menu.

AM-10

Page 10
Image 10
Phonetics SCADA 3000 manual How the Annunciator Module Works