PRIMARY CONTROL OII 350S
SEQUENCE OF OPERATION
The Traeger OII 350S primary control is a
FUSE
RED LIGHT
INDICATOR
ON TIME (2MINUTES)
PILOT CYCLE TIME SWITCH
COMBINATION FUNCTION OF ON TIME AND CYCLE
WIRING
POWER SWITCH
PILOT DRAFT SWITCH
Power In
The computer board is protected by a
When the wall thermostat circuit is closed, and calling for heat, the light indicator will remain dim as long as the circuit is closed. When the thermostat is open (not calling for heat) the light will blink from bright to dim every 15 seconds as part of the counting procedure.
The On Time controls the amount of time the burner stays active (fuel is fed). It operates in conjunction with the cycle time and is
The cycle time switch controls the total cycle both on and off, 8 or 16 minutes.
The On Time is subtracted by the Cycle Time
Example: With the On Time
The 0II350S primary control has 6 lead wires. A wiring colour code is provided on back of each control. Black is line power. White is neutral. Red is load and feeds the auger motor and cup motor. Orange feeds the draft inducer. 2 yellows go to the wall thermostat.
Cuts power to burner but not blower fan system. Used to shut furnace down.
Controls the speed of the draft inducer on pilot or idle mode. Normally set on Medium, but will vary with differing chimney configurations.
16