Option

Description

Sensor Name

Configure the name of a sensor (or device) with up to 15 characters.

 

 

Set Point

The threshold of a sensor (Temperature or Humidity) will trigger an

 

alarm, whenever the measurement is over (high) or under (low) the

 

set point. If the checkbox is not filled, the threshold is disabled and

 

the alarm will not be triggered. The valid range for the Temperature

 

threshold setting is 5 to 65, and 5 to 95 for Humidity.

 

 

Calibration Offset

If the measurement value of a sensor doesn't, for whatever reason,

 

comply with the actual environment, the 'Calibration Offset' setting

 

can be configured to adjust the final value of the sensor. For example,

 

if a sensor reports 43% humidity for a 45% humidity environment, the

 

user can configure the humidity offset as 2% so the sensor can then

 

adjust its final value to 45%.

 

 

Alarm Type

If an alarm sensor (water leak, security, etc) is connected to the IP

 

Power Manager, the user can configure the alarm as 'Disabled',

 

'Normal Open', or 'Normal Close'. A 'Disabled' setting will mean the

 

alarm is inactive. 'Normal Open' and 'Normal Close' are used for a

 

two-wire detector that will emulate an open/close state. When the

 

wires are closed to 'loop-back' (the signal for the sensor), the sensor

 

will detect the state as closed. The sensor will NOT activate the alarm

 

for 'Normal Close' in this case, although the alarm will be activated if

 

configured as 'Normal Open'.

 

 

EMD Status

The EMD can be configured as 'Disabled' or 'Auto'. The setup should

 

be configured as 'Disabled' if an EMD is not attached to the port. The

 

EMD type will be auto detected by the IP Power Manager if

 

configured as 'Auto' and if the EMD is plugged into the port.

 

 

 

- 22 -